Quick Setup Guide
2
kayden.com Online Store
Factory Default:
LOWER
Select the coil operation to energize lower or
higher than setpoint.
Energize Lower than
Setpoint
Energize Higher than
Setpoint
RELAY 1
Press x 1
Factory Default:
LOWER
Press RUN to exit Setup
and return to RUN MODE.
Note: If Bypass is turned on, the
RUN MODE will not start until the
selected time ends
Press SET to enter
Configuration Mode.
To access all 11
menu options, press
SET repeatedly.
Press & Hold RUN + LEFT ARROW +
RIGHT ARROW for 5 seconds to
complete a FACTORY RESET
Select the coil operation to energize lower or
higher than setpoint.
Energize Lower than
Setpoint
Energize Higher than
Setpoint
RELAY 2
Press x 2
Factory Default:
3.0 mA
Select the fault action to be either Fail low at
3.0 mA or Fail high at 21 mA
3.0 mA Output Fault
21.0 mA Output Fault
FAULT
Press x 3
Factory Default:
25%
Select a Thermal Signal Set Point for Relay 1
Decrease Set Point
Increase Set Point
Set Point 1
Press x 4
Factory Default:
75%
Select a Thermal Signal Set Point for Relay 2
Decrease Set Point
Increase Set Point
Set Point 2
Press x 5
Factory Default:
0 Seconds
Select an amount of time for the switch to
return to RUN mode. Increments of 5 seconds.
Decrease Bypass
Time
Increase Bypass
Time
BYPASS
Press x 6
Factory Default:
75%
Select a Heater Power setting. This directly
affects the sensitivity to flow.
Decrease Heater
Power
Increase Heater
Power
RELAY 1
Press x 7
Factory Default:
1
Select a Node Address for Modbus Comms.
Software Rec is also identified on the left LEDs
Decrease Node
Address
Increase Node
Address
RELAY 2
Press x 8
Factory Default:
Forward
Select the action of the 4-20 mA Output to
either Reverse or Forward acting.
Forward Acting mA
Output
Reverse Acting mA
Output
FAULT
Press x 9
Factory Default:
0%
Select a zero percent thermal signal for the
LRV scaled view.
Decrease LRV
Increase LRV
Set Point 1
Press x 10
Factory Default:
100%
Select a one hundred thermal signal for the
URV Scaled View
Decrease URV
Increase URV
Set Point 2
Press x 11
LED SOLID
LED FLASHING
To configure or adjust the CLASSIC, perform the steps in the order indicated.
STEP 1
- Perform changes to Heater Power on Setting 7, then adjust Scaling on Settings 10 & 11
STEP 2
- Push RUN and verify the Thermal Signal is within the unscaled or new scaled view.
STEP 3
- Perform changes to Relay operation on settings 1 & 2
STEP 4
- Perform changes to Set Points on settings 4 & 5
How to Enter, Scroll & Exit the Configuration Menu
How to Perform Factory Reset
Quick Check Buttons
*MUST BE IN
RUN MODE
A
- Press & Hold RUN to view Software Rev & Modbus
Node Address
B
- Press & Hold LEFT ARROW to view LRV and URV.
C
- Press & Hold RIGHT ARROW to view Thermal
Signal on Unscaled Bar Graph
D
- Press & Hold 1 to view Set Point 1
E
- Press & Hold 2 to view Set Point 2
A
D
B
E
C