KT-300 Door Controller Installation Manual

Connecting the Master Controller to the Host 
PC

 Connect flat cable from KT-300 to the PC.

From 0 to 30m (0 to 100 feet):

If the local master controller is located less than 30m 
(100 feet) from the host computer, use the on-board RS-
232 RJ12 jack and the supplied flat cable.

NOTE: 

If you plan to locate the host PC more than 30m 
(100 feet) away from the controller, be sure to 
use a VC-485 interface. Otherwise, reduce the 
communication speed to a minimum to avoid 
data loss.

From 30m to 1.2 km (100 to 4,000 feet)

If the master controller is located more than 60m (200 
feet), an optional VC-485 multi-function communication 
interface must be used. It can also be used when 
running a communication cable in areas unusually high 
in electrical noise.

NOTE: 

The host computer is used to program the KT-
300 Controllers.

Over Corporate Network (LAN)

If the master controller is used in a LAN-enabled corporate setting, use TCP/IP-to-RS-232 
converter (such as the Kantech IP Link or the Lantronix UDS-1100 communication 
interface) to connect the controller to the corporate network. This method uses existing 
wiring for data exchange between EntraPass and the controllers. The diagram on the left 
shows how to connect a DB-9 to RJ-12 flat cable between the master controller and the 
converter. Consult 

Application Note

 DN1506 to learn how to set up the communication 

interface. 

For remote sites

If the master controller is used in remote areas, 
modems must be used to send and receive 
access control data over telephone lines. For this 
application Kantech supports US Robotics 56K 
external Sportster modems at both ends of the 
communication line. As shown on the right, a 
modem connects to the master controller only 
using a DB25 to RJ-12 flat cable. For dial-up 
communication settings via software, refer to 
your communication settings.

RS-232 WITHOUT VC-485

KT-300

VITAL

RJ12F

RS-485 WITH VC-485

CONVERTER

RS-232/RS-485

VC-485

V+ = 5-14 VDC

An optional VC-485 must be used when the PC is located
more than 60m (200”) from the master controller 

P3

EGND

X1-

X1+

+12V

GND

+5V

READER PWR

RS485

C

8

LED BUZ RL1 LED BUZ RL2

OUTDOOR 1

OUTDOOR 2

ORANGE

ORANGE WHITE
BLUE
BLUE WHITE

RED

BLACK

CABLE DESCRIPTION: 1.2 METERS (4”) 
AWG#26, 6 WIRES, INCLUDED WITH
VC-485. (MAX LENGTH 60 METERS (200”))

DB25 (740-1012)
OR
DB9 (740-1022)

KT-300

TB1

16V
AC

+12v-

AUX

LK1-

LK2-

+

LOCK 12V

S/N

*NOTE:

CONNECT A 120 OHMS END
OF LINE RESISTOR ON THE 
LAST KT-300

KT-300

TB2

ORANGE

ORANGE WHITE

BLUE

BLUE WHITE

EGND

X1-

X1+

+12V

GND

+5V

READER PWR

RS485

WHT

+5V

CABLE DESCRIPTION: UNSHIELDED TWISTED PAIR
DATA CABLE, 24 GAUGE ETHERNET GRADE 3,
2 PAIR, BELDEN #1227A

CBLK-20
MAX 60 M (200’)

DB25F
(740-1011)

DB9F
(740-1021)

EntraPass
Gateway

US Robotics Sportster
External 56k

Part# DU-MODEM-HOS

Host Modem Dipswitch Settings
1, 2, 6 UP

(Optional Host Modem
to receive alarms only)

Phone
Jack

Phone
Jack

EntraPass Dial-Up Setup with KT-300

Phone Line

Phone
Jack

US Robotics Sportster
External 56k
Part# DU-MODEM-RS

Remote Modem Dipswitch Settings
1, 6 UP

Adaptor modem
to KT-300 (DB-25)
Part #740-1035

Flat cable
Part #CAB-15

VITAL

RJ12
CONNECTOR

KT-300 MASTER

Содержание Door Controller Innovative and Powerful KT-300

Страница 1: ...DN1315 1007 V01 02 KT 300 Door Controller Installation Manual ...

Страница 2: ......

Страница 3: ... 300 8 Connecting to the RS 485 Bus 8 Connecting the Master Controller to the Host PC 9 Powering the KT 300 10 Installing Combus Modules 10 Introduction to Combus Modules 10 Combus Specifications 10 Combus Repower If Required 11 Module Housing Cabinet 11 KT PC4108 8 Zone Input Expansion Module 12 KT PC4108 Introduction 12 KT PC4108 Specifications 12 Unpacking the KT PC4108 Module 12 Mounting the K...

Страница 4: ...CD 15 Mounting the KT3 LCD 15 Wiring the KT3 LCD 16 Applying Power 16 Assigning the KT3 LCD Keypad 16 Troubleshooting Communication Problems 16 Default Initialization 16 How to Use the Default Initialization Hard Reset 16 VITAL LED status indications 16 Visual Status Indicators LEDs 17 KT 300 Controller Maintenance Recommendations 18 KT 300 Wiring Diagram North American Version 19 KT 300 Wiring Di...

Страница 5: ...n obtained Conditions to Void Warranty This warranty applies only to defects in parts and workmanship relating to normal use It does not cover any of the following the occurrence of which will void this warranty damage incurred in shipping or handling damage caused by disaster such as fire flood wind earthquake or lightning damage due to causes beyond the control of Kantech such as excessive volta...

Страница 6: ...to be repairable will be replaced by the nearest equivalent product available at that time The current market price of the replacement product will be charged for each replacement unit WARNING PLEASE READ CAREFULLY Note to Installers This warning contains vital information As the only individual in contact with system users it is your responsibility to bring each item in this warn ing to the atten...

Страница 7: ... any material on the lenses mirrors windows or any other part of the detection system will impair its proper operation Passive infrared motion detectors operate by sensing changes in temperature However their effectiveness can be reduced when the ambient temperature rises near or above body tem perature or if there are intentional or unintentional sources of heat in or near the detection area Some...

Страница 8: ...age of conductor insulation The power supply must Be permanently connected fail safe with double or reinforced insulation between primary and secondary circuits In EU countries it must meet the applicable requirements of the Low Voltage Directive and protected as per EN60950 1 2006 requirements In other countries it must be of approved type acceptable to local authorities The screwdriver supplied ...

Страница 9: ...or use in security applications system requirements UL Compliance Notice To comply with UL listings the following requirements must be met Use of a UL listed computer Use of UL listed readers Wiegand 26 and 34 bits mag stripe 26 and 34 bits have been tested and found to comply Use of a UL recognized tamper switch on every housing cabinet for the KT 300 Do not use the SmartLink option Use the Kante...

Страница 10: ...tomatically detects the site communication speed set by EntraPass Trouble and Reporting The KT 300 constantly supervises battery condition and reports Low battery or No battery status to the EntraPass system Power outputs are supervised and individually protected against short circuits and surges by self resetting PTC Locking devices are also supervised for short and open circuits Built in Combus ...

Страница 11: ...Types Wiegand proximity bar code magnetic integrated keypad and others Reader Power Output 12 VDC and 5VDC 175mA max protected and supervised Monitored Points 8 monitored points NO NC w without EOL s expandable to 16 use UL recognized tamper switch on cabinet housing to conform with UL 294 Points Maximum Wiring AWG 22 600 meters 2 000 feet Door Strike Power 12 V DC 250mA max each supervised Auxili...

Страница 12: ...t UL listed KT 300ACC Accessory kit including 2 X 1 0k ohm 10 x 5 6k ohm 2 x 120 ohm PCB standoffs lock hole cover ground wire and screwdriver KT PC4108 8 zone input expansion module for KT 300 KT PC4204 4 Relay and Combus additional power supply module for KT 300 KT PC4216 16 Output expansion module for KT 300 KT RM1 External isolation relay SPDT for KT 300 output RL1 RL2 not UL listed KT3 LCD Ti...

Страница 13: ...DN1315 1007 6 KT 300 Door Controller Installation Manual VC 485 or USB 485 Multi function communication interface Kantech Model Description ...

Страница 14: ...the requirements of your local electrical code Wire the E GND terminal on the KT 300 printed circuit board directly to that connection point Door Locking Devices Connect door locks to and LK1 and L2 Maximum 250mA 12 VDC per output Check for local magnetic lock regulations LK1 LK2 and terminals are located on the bottom left to the KT 300 terminal strip The locking device outputs are controlled acc...

Страница 15: ... operating independently to control one way access The distance between the readers and the KT 300 controller varies by reader type please consult the installation manual for details Auxiliary outputs provide visual and or audible access operation feedback at the controlled door Outputs OUT DOOR 1 LED BUZ are used for the first door and OUT DOOR 2 LED BUZ are used for the second door The 12 VDC au...

Страница 16: ...amper switch is required for a UL listed installation Connecting the KT 300 Connecting to the RS 485 Bus Connect RS 485 cable to X1 X1 and GND Controllers are linked together through their RS 485 connectors The maximum communication loop length is 1 2 kilometers 4 000 feet using appropriate cabling Connecting several KT 300 controllers at a single point is not acceptable nor are splitters or spide...

Страница 17: ...sed in remote areas modems must be used to send and receive access control data over telephone lines For this application Kantech supports US Robotics 56K external Sportster modems at both ends of the communication line As shown on the right a modem connects to the master controller only using a DB25 to RJ 12 flat cable For dial up communication settings via software refer to your communication se...

Страница 18: ...ombus Modules The Combus terminals on the KT 300 Controller are used to connect expansion modules to add inputs outputs relays and LCD time and date display The four Combus terminals of the main panel must be connected to the four Combus terminals or wires of all modules Four expansion modules can be connected to KT 300 s Combus more specifications on each of these modules can be found later on in...

Страница 19: ...n section of your EntraPass User Reference Manual for the exact procedure If you are using a KT PC4204 in repower mode and other KT PC4204 modules that are assigned as relays 1 4 or KT PC4216 modules that are assigned as relays 1 16 are also connected to the same loop do not use relay 1 of those modules or relay 1 of the KT 300 door controller Please also note that all KT PC4204 modules that are u...

Страница 20: ...h the circuit board to the cabinet NOTE Wiring may take place once the unit is mounted Installation and Wiring Before wiring the unit ensure that all power sources AC transformer and battery are disconnected from the controller Perform the following steps to complete wiring 1 Connect the four Combus wires to the KT PC4108 Connect the Red Black Yellow and Green Combus wires to the RED BLK YEL and G...

Страница 21: ...stance from the connected devices Perform the following steps to mount the unit 1 Push the five plastic standoffs through the mounting holes on the back of the cabinet 2 Secure the cabinet to the wall in the desired location Use appropriate wall anchors when securing the cabinet to dry wall plaster concrete brick or other surfaces 3 Press the circuit board into the plastic standoffs to secure the ...

Страница 22: ... power drawn from Combus since Combus can handle a maximum of 500 mA a KT PC4204 module in repower mode can be used to increase the current of the Combus of 1A Connects to KT 300 via 4 wire Combus Nominal current draw of 15 mA Tamper contact input Can be used for elevator control Unpacking the KT PC4216 The KT PC4216 package should include the following parts One KT PC4216 circuit board 4 plastic ...

Страница 23: ...witch or the wire if there is no tamper switch NOTE If you are using a KT PC4204 in repower mode on the same loop do not use the first relay of the KT PC4216 KT3 LCD Kantech LCD Time Date Display Module KT3 LCD Introduction The KT3 LCD module is an LCD readout module with integrated keypad which provides date and time via a 32 character liquid crystal display KT3 LCD Specifications Connects to con...

Страница 24: ...nly be followed if a You are using a KT 300 from another site and there is no communication b The KT 300 was communicating via the RS 232 port and you installed a VC 485 to communicate via the RS 485 port c You were using the KT 300 at a local site and now want to configure it for remote operation How to Use the Default Initialization Hard Reset 1 Disconnect both transformer and battery 2 Remove a...

Страница 25: ...RS 485 port LEDs are transmit receive activity indicators RS 232 YELLOW The RS 232 LEDs are ON when communicating to the EntraPass gateway or to the dial up modem COMBUS RX and TX YELLOW These LEDs are transmit receive activity indicators Only very small packets will be sent transmitted upon module activity LOCK1 LOCK2 RED This LED turns ON when the lock output is activated RELAY1 RELAY2 RED Each ...

Страница 26: ...o not apply pressure to or deform the batteries Ensure that the above precautions are strictly observed by related departments including but not limited to production sales and outside contractors Regarding the recommended battery 7 A 12 V It is the end user and or installer responsibility to assure that the disposal of used batteries is made according to the waste recovery and recycling regulatio...

Страница 27: ...DN1315 1007 20 KT 300 Door Controller Installation Manual KT 300 Wiring Diagram North American Version ...

Страница 28: ...DN1315 1007 21 KT 300 Door Controller Installation Manual KT 300 Wiring Diagram EU Version ...

Отзывы: