LET-BY & TIGHTNESS TESTING
Rotate dial to “Tightness” & press
to auto zero pressure sensor.
Using the black connectors, connect your manometer hose from the
appliance’s test point to your analyser’s P1 input.
Display shows “LET BY?” – use &
to select YES or NO.
If YES is selected, set the let-by pressure then press
to start the
let-by test – display shows:
If let-by test fails rotate dial to another position to stop the test.
If Let-by test passes, adjust gas pressure for the tightness test & press
to start the stabilisation test – display shows:
When complete press
to start the tightness test:
Let-by test is automatically stored in
memory
Pressure at start of let-by test
Real time reading
Let-by default time is 60 seconds – can
be changed via “Menu”
Real time pressure reading
Stabilisation default time is 60 seconds