24 KANE 358 MANUAL
PRESSURE MEASUREMENT GOOD PRACTICE
WARNING
Before using the KANE358 to measure an appliance’s gas/air ratio
valve, read the appliance manufacturer’s instructions thoroughly. If in
doubt contact the appliance manufacturer.
After adjusting a gas/air ratio valve it is essential CO, CO₂ & CO/CO₂
ratio readings are within the appliance manufacturer’s specified limits.
LARGE BORE TUBING ISSUES
If using large bore tubing when performing pressure tests:
Push orange tube over rim of spigot to
ensure a gas tight seal.
This may not produce a gas tight seal.
COMMISSIONING TEST
Your analyser’s commissioning test uses the test outlined in the
UK’s TB143 but is not a substitute for an appliance manufacturer’s
instructions.
Rotate dial to TESTS position. Press the followed by the
& follow
your analyser’s instructions.
TEST 1 – CHECK THE APPLIANCE AT MAX GAS RATE
Switch on appliance to max rate & zero your analyser in outside fresh air.