3.1 Mou
nting the flo
w sensor
The flow sen
sor
can be
mount
ed
ver
tical
ly,
horizont
ally
or
at an an
gle.
The flow sen
sor
can be t
urned
upw
ards
to m
ax.
45
°
and
down
war
ds
to m
ax. 90
°
in
rel
ation to the pipe
axis.
Do not
mount
the flow sen
sor
with the p
las
tic
box up
war
ds.
1. General information
Please read these instructions before installing the heat me-
ter. Kamstrup’s guarantee obligations do not apply in case
of incorrect installation.
Please note the following installation requirements:
Gland meters
Max. 16 bar
1.1 MID designations
Rated operation conditions/measuring ranges:
Temperature of medium in flow sensor: 0.1°C…30°C
Mechanical environment: M1 (fixed installation with minimum
vibration)
Electromagnetic environment: E1 (Domestic and light indu-
strial). Signal cables from the meter must be separated by at
least 25 cm distance to other installations.
Climatic environment: The installation shall be made in non-
condensing environments and in closed location (indoor). The
ambient temperature must be within 5…55°C.
Maintenance and repair:
The water supplier is allowed to change communication module
and battery. The flow part must never be separated from the
calculator. All repairs require a following re-verification on an
accredited laboratory.
Battery for replacement: Kamstrup type 66-00-200-100.
Kams
trup A/S
Industriv
ej 28, Sti
llin
g
DK-8660
Skanderbor
g
TEL: +45 89 93 10 00
FAX:
+45 89 93 10 01
info@k
amstrup
.com
www.k
amstrup
.com
Inst
allation
MULTICAL
®
41 W
ater M
eter
Engli
sh
2. Information codes “E”
MULTICAL
®
41 constantly monitors a number of important func-
tions. If a serious error occurs in the metering system or in the
installation, an “E” appears in the left side of the display and an
information code can be read by activating the front key until an
“E” appears in the right side of the display.
Information
code
Description
Response
time
000
No irregularities
–
016
Air in the flow sensor
128
Battery replacement
12 years
3. Mounting of flow part
Before mounting the flow part (flow sensor), flush the system
thoroughly and remove protection plugs/plastic membranes
from the flow sensor.
The flow direction is indicated by an arrow on the side of the
flow sensor.
There are no requirements for straight inlet, but we recommend
a straight inlet of 3…5
×
DN.
To prevent cavitation the operating pressure at the flow sensor
must be min. 1.5 bar at Q3 and min. 2.5 bar at Q4.
The flow sensor must not be exposed to pressures below
ambient pressures (vacuum).
4.
Mountin
g the calc
ulat
or
4.1 Mou
nting
MULTICAL
®
41 mu
st be mou
nted on the w
all due t
o the risk
of c
ondensation in the el
ectronic
s p
art.
Use the fittin
gs a
s a t
emplat
e for m
arkin
g-out
and drill 2 pc
s.
hole
s of
6 mm in the wal
l. Af
ter mou
nting the c
alcul
ator i
s
seal
ed with se
al and thr
ead.