MULTICAL®
403
Kamstrup
A/S
∙
Technical
description
∙
5512
‐
1689_B1_GB_03.2017
103
MULTICAL®
403
connected
to
24
VAC
incl.
transformer
(6699
‐
403)
MULTICAL®
403
connected
to
24
VAC
excl.
transformer
MULTICAL®
403
direct
connected
to
230
VAC
Gained
power
[W]
<
1.5
W
<
1
W
<
1
W
Apparent
power
[VA]
<6
VA
<7
VA
<11.5
VA
Yearly
consumption
[kWh]
Approx.
13
kWh
Approx.
9
kWh
Approx.
9
kWh
10.7
Transformer
230/24
VAC
The
supply
modules
for
24
VAC
are
adjusted
for
use
with
a
230/24
VAC
safety
transformer
e.g.
Kamstrup
type
6699
‐
403,
which
is
mounted
in
a
control
panel
or
another
separate
capsuling.
Regarding
power
consumption
using
a
safety
transformer
in
connection
with
24
VAC
supply
modules,
see
paragraph
10.6
regarding
power
consumption
of
mains
connected
meters.
Maximum
cable
length
between
230/24
VAC
transformer
e.g.
Kamstrup
type
6699
‐
403
and
MULTICAL
®
.
10.8
Supply
cables
for
supply
module
MULTICAL®
403
can
be
supplied
with
supply
cable
type
H05
VV
‐
F
1
2
x
0.75
mm²
to
be
used
for
both
24
and
230
VAC,
if
required
by
the
customer.
The
supply
cable
to
the
meter
must
not
be
protected
by
a
larger
fuse
than
permitted,
6
A
fuse
for
2
x
0.75
mm²
cable
(accessory
from
Kamstrup
A/S,
type
50
‐
00
‐
286).
Alternatively
a
2
x
1.0
mm²
supply
cable
can
be
used
with
a
10
A
fuse.
In
connection
with
other
installation
types
or
if
a
larger
fuse
than
10
A
is
required,
it
is
necessary
to
consult
a
certified
electrician
for
an
evaluation
of
how
the
type
of
installation
in
question
should
be
carried
out
in
terms
of
safety.
1
H05 VV‐F is the type designation of PVC‐isolated cable, with a nominal voltage of 300/500 V and a max.
temperature of 70
°C. During installation please remember to keep sufficient distance to hot parts of the installation.
Cable
type
Maximum
length
2
x
0.75
m
50
m
2
x
1.5
mm
2
100
m