46
Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains
Electrical wiring |
UniLine EC, KaControl model (*C1)
All KaControl units have multifunctional inputs that can be assigned
different functions during commissioning, e.g. an internal temperature
sensor in the unit for frost protection monitoring.
Connect the cables in accordance with the wiring diagram and use the
KaController to configure the functions.
10.8.5 Internal unit temperature sensor
All KaControl master units have an analogue input to connect an
external room temperature sensor.
Connect the cables in accordance with the wiring diagram and use the
Dip switch and KaController to configure the functions.
The maximum cable length between the master unit and the room
temperature sensor is 30 m.
All KaControl master units have multifunctional inputs that can be
assigned different functions during commissioning.
Connect the cables according to the wiring diagram and configure the
functions by means of the KaController.
The maximum cable length between the master unit and the external
potential-free contacts is 30 m.
10.8.3 External room temperature sensor
10.8.4 Inputs for processing external contacts
(e.g. on-site BMS etc.)
Mains
230V/50 Hz
Mains
230V/50 Hz
3
2**
2**
2**
2**
3
Master
unit
#1
Slave unit
#2
Bus connection 30 m
Maximum length
** Route shielded, paired
cables, e.g. CAT5
(AWG23) of at least the
same value separately
from high-voltage
cables.
It is not possible to connect an external room temperature
sensor to the slave units. Set the DIP switch no. 6 to OFF when
using an external room temperature sensor on a master unit.
No external contacts (e.g. window contact, card reader etc.) can
be connected to the slave units.
Set the DIP switch no. 3 to ON when using an internal
temperature sensor in the unit.
Mains
230V/50 Hz
Mains
230V/50 Hz
3
2**
2**
2**
3
Master
unit
#1
Slave unit
#2
Bus connection 30 m
Maximum length
** Route shielded, paired
cables, e.g. CAT5
(AWG23) of at least the
same value separately
from high-voltage
cables.
Mains
230V/50 Hz
Mains
230V/50 Hz
3
2**
2**
3
Master
unit
#1
Slave unit
#2