Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains
Electrical wiring |
UniLine EC, electromechanical model
with external fault signalling (*T)
10.4 UniLine EC, electromechanical model with external fault signal (*T)
Description of switches:
The mains voltage is wired to the voltage supply terminals on the door
air curtain.
Continuously variable speed control via an active 0…10 VDC signal or
potentiometer.
Internal evaluation of a possible motor fault and switch off of the EC
fans and potential-free fault signal contact.
Setting option for maximum speed of EC fans via potentiometer.
The heating valve (if fitted) can be opened or closed by the compact
controller type 30158 or an on-site switch command.
Dip switch setting on the PCB
Technical details for inputs/outputs on the PCB
Input impedance 0 -10 ≥100 kΩ
Fault signal contact: U = max. 60 VAC/DC
I = max. 1A
Fuse F1:
1A
Fuse F2:
4A
Compact controller
Combination of operating mode selector switch and speed sensor with
options for external control and operation.
The required room temperature is set on the compact controller.
The door air curtain is disabled in standby mode. A frost protection function
can be activated by means of settings. In winter mode the fan speed can be
set by the dial and the actuator is open. In summer mode the fan speed can
be set by the dial and the actuator is closed.
The fan can be allowed to run on or increase the speed by connecting a
door contact switch and corresponding parametrisation. Additionally, a
room temperature control can be activated, which closes the hot water
valve and disables the fan when the set temperature is reached.
Compact controller in a flat surface-mounted housing, white
Rating IP 30, voltage 230 V/50 Hz
Dimensions W x H x D: 110 x 110 x 27 mm
DIP
Factory
setting
Function
Functional descriptions
1
OFF
Speed signal
OFF: active 0-10 V signal
ON: Potentiometer 0-100 kΩ
2
ON
Speed signal
OFF: Potentiometer 0-100 kΩ
ON: active 0-10 V signal
Valve drive
Valve drive
Fault message
Control signal
Feed line