Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains
Electrical wiring |
UniLine EC, KaControl model (*C1)
A14 Condensation alarm
The condensation alarm of a unit is shown on the KaController by the
display "A14". A unit with an active condensation alarm automatically
closes all valves.
Check that the condensation pump is running correctly and check the water
level in the condensation tank if a condensation alarm occurs.
Effect of this alarm:
The heating valve opens and fan stage 1 is switched on.
A15 General alarm
The general alarm with units with KaControl is only triggered if the inputs
on the KaControl have been correspondingly parametrised.
Effect of this alarm:
The heating valve opens and fan is switched on.
A16 Faulty AI1, AI2 or AI3 sensor
The sensor alarm is displayed if one of the active sensors does not transmit
any plausible measured values to the KaControl. Check the correct wiring of
the KaControl and check the sensor.
Effect of this alarm:
The heating valve opens and fan is switched on.
A17 Unit frost protection function
The temperature at the temperature sensor is monitored at each phase in
the system to a limit of 4 °C. The unit frost protection function is activated
if the temperature drops below 4°C. The heating valve opens and fan is
switched on.
The unit frost protection function is disabled when the temperature at the
sensor rises above the limit of 4°C. The unit frost protection function is also
activated if the room temperature drops below 4°C.
Effect of this alarm:
The heating valve opens and fan is switched on.
The limit of 4 °C is fixed for the unit frost protection function
and cannot be changed.