OWDMANUAL 1114
KAM CONTROLS, INC.
15
I N S TA L L AT I O N C O N T I N U E D
Measure the calculated MID from the top of the
Locking Collar and place a mark with a permanent
marker or tape on the Shaft. FIG. 3-18.
5.
MID
6.
Bolt or screw the OWD
®
sensor to the valve or designated installation location.
(KAM CONTROLS recommends using thread sealant and not Teflon tape for the threaded OWD
®
).
Open full opening valve.
7.
Loosen Socket Cap Screws on the locking collar.
8.
FIG. 3-10
Push OWD
®
sensor in until the mark is at the top edge of the locking collar. Ensure that OWD
®
flow indicator is
aligned with pipeline flow direction. FIG. 3-19.
9.
Mark
Re-tighten the Socket Cap Screws.
Tighten the hex nuts holding down the Locking Collar one half turn. (Fig. 3-19) These should never be over-tight-
ened. Their major function is to apply light pressure on the chevron packing to ensure a seal between the seal
housing body and the insertion shaft.
10.
11.
REMOVING THE OWD
®
SENSOR
To remove the OWD
®
sensor, first shut off power to the instrument. Loosen the Socket Cap Screw on the Lock Down
Collar. Slide the OWD
®
sensor upward until the probe rests inside the seal housing. Next, close the Full-opening Ball
Valve tightly. Drain oil from valve if possible. The OWD
®
sensor may now be unbolted from the system.
Note: If line pressure exceeds 100 psi, use a KAM
®
IT Insertion Tool when installing/removing
the KAM
®
OWD
®
sensor.
Removal should be conducted in accordance with all regional and Class requirements.
FIG. 3-11
Hex Nuts