Troubleshooting
154
Electrical Control System
2.4.4.15. P6 malfunction (For three phases units)
At first test the resistance between every two ports of U, V, W of IPM and P, N. If any result of them is 0 or
close to 0, the IPM is defective. Otherwise, please follow the procedure below:
P6 display
IPM module protection
Check whether the voltage
range of P-N on IPM module is
normal? DC 350-650V
Yes
Yes
No
Yes
Check whether the
input power supply is
correct? 380-415V, 3N,
50Hz
No
No
Regulate it to correct,
then check whether the
system can work
normally?
Check whether the
power supply line is
connected correctly
and tightly
Yes
Connect it correctly
and tightly, check ok
or not?
No
Check whether the
connecting line between main
board and the IPM module is
connected tightly
Yes
Connect it tightly,
check ok or not?
No
No
No
Connect it well,
check ok or not?
Check whether the
connecting line of the
compressor is connected
correctly or tightly
Replace the IPM module,
check whether the system
can work normally?
No
No
Replace the main board;
check whether the system
can work normally?
No
Replace the compressor,
check whether the system
can work normally?
Yes
Yes
Check whether the
lines in E-part box are
connected tightly
Yes
Connect it tightly,
check ok or not?
No
No
Yes
No
Replace the bridge rectifiers
Check whether the bridge rectifiers
are normal? Use the multimeter to
measure the resistance between
each two terminals, check whether
there is the condition that value of
resistance is 0
Check whether the 3300µF/400V
electrolytic capacitor is normal?
Replace this electrolytic
capacitor
Yes
No
No
Yes
Trouble is solved
Содержание KOU-12HFN1-QRC8
Страница 1: ...Contents i Energy Related Products SUPER DC INVERTER SERIES Service Manual 2013 LFIS B 1309...
Страница 2: ......
Страница 4: ......
Страница 17: ...Service Space Indoor Units 13 3 Service Space 1000mm 1000mm 1000mm 1000m m...
Страница 23: ...Field Wiring Indoor Units 19 9 Field Wiring...
Страница 31: ...Wiring Diagrams Indoor Units 27 KTB 24HWDN1 QRC4...
Страница 42: ...Service Space 38 Indoor Units 3 Service Space...
Страница 44: ...Wiring Diagrams 40 Indoor Units KUE 36HRFN1 QRC8 A...
Страница 47: ...Indoor Units 43 9 Field Wiring...
Страница 50: ...Dimensions 46 Indoor Units 2 Dimensions...
Страница 51: ...Service Space Indoor Units 47 3 Service Space...
Страница 52: ...Wiring Diagrams 48 Indoor Units 4 Wiring Diagrams KCA2U 12HRFN1 QRC8 KCA2 18HRFN1 QRC8...
Страница 56: ...52 Indoor Units 10 Field Wiring KCA2U 12HRFN1 QRC8 KCA2 18HRFN1 QRC8...
Страница 58: ......
Страница 61: ...Dimensions Console Type 57 2 Dimensions KFAU 12HRFN1 QRC8 KFA 16HRFN1 QRC8...
Страница 62: ...Service Space 58 Console Type 3 Service Space...
Страница 63: ...Wiring Diagrams Console Type 59 4 Wiring Diagrams KFAU 12HRFN1 QRC8 KFA 16HRFN1 QRC8...
Страница 68: ...Field Wiring 64 Console Type 10 Field Wiring KFAU 12HRFN1 QRC8 KFA 16HRFN1 QRC8...
Страница 74: ...Wiring Diagrams 70 Outdoor Units 4 Wiring Diagrams KOU 12HFN1 QRC8...
Страница 76: ...Wiring Diagrams 72 Outdoor Units KOU 36HFN1 RRC4 KOU 36HFN1 RRC8 520 KOU 36HFN1 QRC8 5A0...
Страница 77: ...Wiring Diagrams Outdoor Units 73 KOU 36HFN1 RRC8 5A0...
Страница 102: ...Refrigerant pipe installation 98 Installation...
Страница 110: ...Engineering of insulation 106 Installation cause leakage to damage the house decoration...