Drainage pipe installation
Installation
101
Indoor
unit
More than 50mm
More than 25mm
Plug
Water storage pipe
6.2.7 Lifting pipe setting of indoor unit with water pump
The length of lifting pipe should not exceed the pump head of indoor unit water pump.
Pump head of big four way cassette: 750mm
Pump head of compact four way cassette: 500mm
The drainage pipe should be set down inclined after the lifting pipe immediately to avoid wrong
operation of water level switch.
Refer the following picture for installation reference.
Flexible pipe 300mm
Hanger
A
A:Length of horizontal pipe
≤
150mm
B: Lift height
≤
the pump head of water pump
Down incline pipe
B
6.2.8 Blowhole setting
For the concentrated drainage pipe system, there should design a blowhole at the highest point of main
pipe to ensure the condensate water discharge smoothly.
The air outlet shall face down to prevent dirt entering pipe.
Each indoor unit of the system should be installed it.
The installation should be considering the convenience for future cleaning.
Blowhole
Plug
Indoor unit
Plug
Indoor unit
6.2.9 The end of drainage pipe shall not contact with ground directly.
Содержание KOU-12HFN1-QRC8
Страница 1: ...Contents i Energy Related Products SUPER DC INVERTER SERIES Service Manual 2013 LFIS B 1309...
Страница 2: ......
Страница 4: ......
Страница 17: ...Service Space Indoor Units 13 3 Service Space 1000mm 1000mm 1000mm 1000m m...
Страница 23: ...Field Wiring Indoor Units 19 9 Field Wiring...
Страница 31: ...Wiring Diagrams Indoor Units 27 KTB 24HWDN1 QRC4...
Страница 42: ...Service Space 38 Indoor Units 3 Service Space...
Страница 44: ...Wiring Diagrams 40 Indoor Units KUE 36HRFN1 QRC8 A...
Страница 47: ...Indoor Units 43 9 Field Wiring...
Страница 50: ...Dimensions 46 Indoor Units 2 Dimensions...
Страница 51: ...Service Space Indoor Units 47 3 Service Space...
Страница 52: ...Wiring Diagrams 48 Indoor Units 4 Wiring Diagrams KCA2U 12HRFN1 QRC8 KCA2 18HRFN1 QRC8...
Страница 56: ...52 Indoor Units 10 Field Wiring KCA2U 12HRFN1 QRC8 KCA2 18HRFN1 QRC8...
Страница 58: ......
Страница 61: ...Dimensions Console Type 57 2 Dimensions KFAU 12HRFN1 QRC8 KFA 16HRFN1 QRC8...
Страница 62: ...Service Space 58 Console Type 3 Service Space...
Страница 63: ...Wiring Diagrams Console Type 59 4 Wiring Diagrams KFAU 12HRFN1 QRC8 KFA 16HRFN1 QRC8...
Страница 68: ...Field Wiring 64 Console Type 10 Field Wiring KFAU 12HRFN1 QRC8 KFA 16HRFN1 QRC8...
Страница 74: ...Wiring Diagrams 70 Outdoor Units 4 Wiring Diagrams KOU 12HFN1 QRC8...
Страница 76: ...Wiring Diagrams 72 Outdoor Units KOU 36HFN1 RRC4 KOU 36HFN1 RRC8 520 KOU 36HFN1 QRC8 5A0...
Страница 77: ...Wiring Diagrams Outdoor Units 73 KOU 36HFN1 RRC8 5A0...
Страница 102: ...Refrigerant pipe installation 98 Installation...
Страница 110: ...Engineering of insulation 106 Installation cause leakage to damage the house decoration...