62
4.Mailing address
Address
Functio
n
Number
Content
mode
Default
Description
Remark
1011
03/06
Power on/off
read/write
0-OFF/1-ON
DIGI1
1012
03/06
Mode
read/write
H05=1
:
0-Hot water/1-Heating/2-Cooling/3-Hot
water + heating/4-Hot water + Cooling
H05=0
:
0-Hot water/1-Heating/3-Hot water +
heating
DIGI1
1045
03/06
Forced switching time for heating water
read/write
120
1~180min
DIGI1
1157
03/06
H32
Domestic hot water target temperature
read/write
55
R36-R37
TEMP1
1158
03/06
R01
Heating target temperature
read/write
45
R10~R11
TEMP1
1159
03/06
R02
Cooling target temperature
read/write
7
R08~R09
TEMP1
1160
03/06
R03
Heating start-up return difference
read/write
2
0~10
℃
TEMP1
1161
03/06
R04
Heating constant temperature shutdown
temperature difference
read/write
1
0~10
℃
TEMP1
1173
03/06
R05
Use of electric heating
read/write
0
0-No electric heating/1-water circuit electric
heating/2-water tank electric heating
DIGI1
1174
03/06
R35
Cooling start-up return difference
read/write
2
0.0~10.0
℃
TEMP1
1175
03/06
R06
Cooling constant temperature shutdown
temperature difference
read/write
1
0.0~10.0
℃
TEMP1
1193
03/06
R07
Operating ambient temperature of main circulating
pump
read/write
2
-10~20
℃
TEMP1
1194
03/06
R40
Operating ambient temperature of air conditioning
pump
read/write
2
-10~20
℃
TEMP1
1195
03/06
R41
Hot water start-up return difference
read/write
5
0~10
℃
TEMP1
1196
03/06
R16
Hot water constant temperature shutdown
temperature difference
read/write
2
0~10
℃
TEMP1
1197
03/06
R17
Operating mode of circulating water pump
read/write
2
0-normal/1-special/2-intermittent
TEMP1
1198
03/06
P01
Circulating water pump operation time interval
read/write
30
1~120min
DIGI1