68
2087
16
write
bit0
:
Reserved
bit1
:
Reserved
bit2
:
Reserved
bit3
:
Reserved
bit4:
S
ystem 1 high-voltage protection for 3
times or more (0-no/1-yes)
bit5
:
Reserved
bit6: System 1 low-voltage protection for 3
times or more (0-no/1-yes)
bit7
:
Reserved
bit8: Water flow switch protection for 3 times
or more (0-no/1-yes)
bit9: Electric heating overheating protection
for 3 times or more (0-no/1-yes)
bit10
:
Reserved
bit11
:
Reserved
bit12: System 1 anti-freezing protection for 3
times or more (0-no/1-yes)
bit13
:
Reserved
bit14
:
Reserved
bit15
:
Reserved
DIGI1
2088
16
write
bit0:
S
ystem 1 exhaust over-temperature
protection for 3 times or more (0-no/1-yes)
bit1
:
Reserved
bit2: Excessive inlet and outlet water
temperature difference failure 3 times or more
(0-no/1-yes)
bit3: Outlet water temperature too low
protection for 3 times or more (0-no/1-yes)
bit4: Outlet water temperature too high
protection for 3 times or more (0-no/1-yes)
bit5
:
Reserved
bit6
:
Reserved
DIGI1