3.IPM continuity check
Turn off the power, let the large capacity electrolytic capacitors discharge completely, and dismount the IPM.
Use a
digital tester to measure the resistance between P and UVWN; UVW and N.
Digital tester
Normal resistance value
(+)Red
(-)Black
∞
(Several MΩ)
P
N
U
V
W
Digital tester
Normal resistance value
(+)Red
(-)Black
∞
(Several MΩ)
U
N
V
W
4.Indoor AC Fan Motor
Measure the resistance value of each winding by using the tester.
Position
Resistance Value
RPG20E
RPG45C
Black - Red
430
Ω±8% (20
℃
)
168
Ω±8% (20
℃
)
White - Black
370
Ω±8% (20
℃
)
141
Ω±8% (20
℃
)