 Page 21 

Indoor Unit 

Installation

Step 4: Prepare refrigerant piping

The refrigerant piping is inside an insulating 
sleeve attached to the back of the unit. You 
must prepare the piping before passing it 
through the hole in the wall. 

1.  Based on the position of the wall hole relative 

to the mounting plate, choose the side from 
which the piping will exit the unit. 

2.  If the wall hole is behind the unit, keep the 

knock-out panel in place. If the wall hole is to 
the side of the indoor unit, remove the plastic 
knock-out panel from that side of the unit.
This will create a slot through which your 
piping can exit the unit. Use needle nose pliers 
if the plastic panel is too difficult to remove by 
hand.    

3.

 

If existing connective piping is already 

embedded in the wall, proceed directly to 

the 

Connect Drain Hose

 step. If there is no  

embedded piping, connect the indoor unit’s 

refrigerant piping to the connective piping 

that will join the indoor and outdoor units. 

Refer to the 

Refrigerant Piping Connection

 

 

section of this manual for detailed instructions.

NOTE ON PIPING ANGLE

Refrigerant piping can exit the indoor unit from 

four different angles:Left-hand side,Right-hand 
side, Left rear, Right rear. 

  

Knock-out Panel

 CAUTION

Be extremely careful not to dent or damage 
the piping while bending them away from
the unit. Any dents in the piping will affect 
the unit’s performance. 

Step 5:

 

Connect drain hose

By default, the drain hose is attached to the left-

hand side of unit (when you’re facing the back 

of the unit). However, it can also be attached to 

the right-hand side. To ensure proper drainage, 
attach the drain hose on the same side that your 
refrigerant piping exits the unit. Attach drain hose 
extension (purchased separately) to the end of 
drain hose.  

 

 

Wrap the connection point firmly with Teflon
tape to ensure a good seal and to prevent leaks. 

 

Remove the air filter and pour a small amount 

of water into the drain pan to make sure that 

water flows from the unit smoothly.

 NOTE ON DRAIN HOSE
 PLACEMENT 

Make sure to arrange the drain hose 

according to the following figures. 

.

PLUG THE UNUSED DRAIN HOLE

To prevent unwanted leaks 
you must plug the unused 
drain hole with the rubber 
plug provided. 

CORRECT 

Make sure there are no kinks
or dent in drain hose to ensure 
proper drainage.   

NOT CORRECT

Kinks in the drain hose 

will create water traps.

NOT CORRECT

Do not place the end of the 
drain hose in water or in 
containers that collect water. 
This will prevent proper 
drainage.     

NOT CORRECT

Kinks in the drain hose 

will create water traps.

For the portion of the drain hose that will remain
indoors, wrap it with foam pipe insulation to 
prevent condensation. 

Содержание ICE KLB

Страница 1: ...ng your new air conditioning unit Make sure to save this manual for future reference Please check the applicable models technical data F GAS if any and manufacturer information from the Owner s Manual...

Страница 2: ......

Страница 3: ...Owner s Manual Table of Contents Safety Precautions 03 Care and Maintenance 11 Troubleshooting 13 1 Indoor unit display 07 2 Operating temperature 08 3 Other features 09 4 Setting angle of airflow 10...

Страница 4: ...t 24 Outdoor Unit Installation 25 1 Select installation location 25 2 Install drain joint 26 3 Anchor outdoor unit 26 4 Connect signal and power cables 28 Refrigerant Piping Connection 29 A Note on Pi...

Страница 5: ...rods or other objects into the air inlet or outlet This may cause injury since the fan may be rotating at high speeds Do not use flammable sprays such as hair spray lacquer or paint near the unit Thi...

Страница 6: ...exceeding 30mA and disconnection must be incorporated in the fixed wiring in accordance with the wiring rules For all electrical work follow all local and national wiring standards regulations and th...

Страница 7: ...o not install the unit within 1 meter 3 feet of any combustible materials Do not install the unit in a location that may be exposed to combustible gas leaks If combustible gas accumulates around the u...

Страница 8: ...waste electrical and eletrical equipment should not be mixed with general household waste 2 2 2 2 2 When flammable refrigerant are employed appliance shall be stored in a well ventilated area where t...

Страница 9: ...r On Back of Main Filter Some Units Louver Front Panel when Active Clean feature is turned on For Inverter split type fresh defrost run timer Display window Displays temperature operation feature and...

Страница 10: ...2 F 15 C 24 C 5 F 75 F 0 C 50 C 32 F 122 F 0 C 52 C 32 F 126 F For special tropical models 0 C 52 C 32 F 126 F For special tropical models 15 C 50 C 5 F 122 F For models with low temp cooling systems...

Страница 11: ...professional staff Set temperature 1hr 1hr Keep running SLEEP Operation Saving energy during sleep Heat mode 1 C 2 F per hour for the first two hours Cool mode 1 C 2 F per hour for the first two hour...

Страница 12: ...ecome out of sync If this occurs turn off the unit and unplug it for a few seconds then restart the unit This will reset the louver Range The horizontal angle of the airflow must be set manually Grip...

Страница 13: ...the unit Do not use benzene paint thinner polishing powder or other solvents to clean the unit They can cause the plastic surface to crack or deform Do not use water hotter than 40 C 104 F to clean th...

Страница 14: ...If you plan not to use your air conditioner for an extended period of time do the following Clean all filters Turn on FAN function until unit dries out completely Turn off the unit and disconnect the...

Страница 15: ...Troubleshooting Troubleshooting The unit changes from COOL HEAT mode to FAN mode The indoor unit makes noises A rushing air sound may occur when the louver resets its position A squeaking sound may o...

Страница 16: ...customer service center Provide them with a detailed description of the unit malfunction as well as your model number Troubleshooting Troubleshooting When troubles occur please check the following po...

Страница 17: ...oor heating performance The outdoor temperature is extremely low Use auxiliary heating device Cold air is entering through doors and windows Make sure that all doors and windows are closed during use...

Страница 18: ...Shape Quantity PC Need to be installed on the back of main air filter by the authorized technician while installing the machine Mounting plate fixing screw Remote controller Fixing screw for remote co...

Страница 19: ...g Plate Determine Wall Hole Position 1 2 3 Drill Wall Hole 4 12cm 4 75in 2 3m 90 55in 12cm 4 75in 15cm 5 9in Mount Indoor Unit STEP 8 Wrap Piping and Cable not applicable for some locations in North A...

Страница 20: ...requirement of local and national standards The installation may be slightly different in different areas Wall Mounting Plate Power Cable Some Units Refrigerant Piping Signal Cable Remote Controller...

Страница 21: ...irect sunlight NOTE ABOUT WALL HOLE If there is no fixed refrigerant piping While choosing a location be aware that you should leave ample room for a wall hole see Drill wall hole for connective pipin...

Страница 22: ...When the gas side connective pipe is 16mm 5 8in or more the wall hole should be 90mm 3 54in Left rear wall hole 65mm 2 5in Left rear wall hole 65mm 2 5in Left rear wall hole 65mm 2 5in Left rear wall...

Страница 23: ...extremely careful not to dent or damage the piping while bending them away from the unit Any dents in the piping will affect the unit s performance Step 5 Connect drain hose By default the drain hose...

Страница 24: ...ly resolved 4 Power voltage should be within 90 110 of rated voltage Insufficient power supply can cause malfunction electrical shock or fire 5 If connecting power to fixed wiring a surge protector an...

Страница 25: ...p to fasten the signal cable to the unit Screw the cable clamp down tightly 8 Replace the wire cover on the front of the unit and the plastic panel on the back DRAIN HOSE MUST BE ON BOTTOM Make sure t...

Страница 26: ...pressure to the left and right hand sides of the unit The unit should not jiggle or shift 6 Using even pressure push down on the bottom half of the unit Keep pushing down until the unit snaps onto th...

Страница 27: ...that air outlet fan is at a 90 angle to the direction of the wind If needed build a barrier in front of the unit to protect it from extremely heavy winds See Figures below Strong wind Strong wind Stro...

Страница 28: ...bber seal see Fig B do the following 1 Insert the drain joint into the hole in the base pan of the unit The drain joint will click in place 2 Connect a drain hose extension not included to the drain j...

Страница 29: ...lled holes 5 Remove the nuts from expansion bolts and place outdoor unit on bolts 6 Put washer on each expansion bolt then replace the nuts 7 Using a wrench tighten each nut until snug WARNING WHEN DR...

Страница 30: ...ock 5 Ground the unit in accordance with local codes 6 Be sure to size each wire allowing several inches longer than the required length for wiring 7 Use lock nuts to secure the conduit tubes BEFORE P...

Страница 31: ...This will drastically reduce the heating efficiency of the unit Maximum Length and Drop Height of Refrigerant Piping per Unit Model Refrigerant piping Connection Refrigerant Piping Connection The leng...

Страница 32: ...rs from falling into the pipe 2 Using a reamer or deburring tool remove all burrs from the cut section of the pipe Pipe Reamer Point down Step 3 Flare pipe ends Proper flaring is essential to achieve...

Страница 33: ...0 76 0 78 23 2 23 7 0 91 0 93 18 20 180 200kgf cm 32 39 320 390kgf cm 49 59 490 590kgf cm 57 71 570 710kgf cm 67 101 670 1010kgf cm 9 52 0 375 12 7 0 5 16 0 63 19 0 75 1 Unscrew the cover from the pa...

Страница 34: ...for at least 15 minutes or until the Compound Meter reads 76cmHG 10 Pa 2 3 4 5 5 6 Close the Low Pressure side of the manifold gauge and turn off the vacuum pump 7 Wait for 5 minutes then check that...

Страница 35: ...AUTION DO NOT mix refrigerant types ADDITIONAL REFRIGERANT PER PIPE LENGTH Connective Pipe Length m Air Purging Method Additional Refrigerant Standard pipe length Vacuum Pump N A Standard pipe length...

Страница 36: ...Water Method Using a soft brush apply soapy water or liquid detergent to all pipe connection points on the indoor unit and outdoor unit The presence of bubbles indicates a leak Leak Detector Method If...

Страница 37: ...it will increase This may reveal leaks that were not present during your initial leak check Take time during the Test Run to double check that all refrigerant pipe connection points do not have leaks...

Страница 38: ...ging bag Outdoor Unit 1 Cut the packing belt 2 Take the unit out of the carton 3 Remove the foam from the unit 4 Remove the packaging bag from the unit Packing Indoor unit 1 Put the indoor unit into t...

Страница 39: ......

Страница 40: ...cations are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service website p...

Отзывы: