background image

Outdoor Unit 

Installation

 Page 28

 

 

 

Step 4: Connect signal and power cables

The outside unit’s terminal block is protected by 

an electrical wiring cover on the side of the unit. 

A comprehensive wiring diagram is printed on 

the inside of the wiring cover.

 WARNING

 

 

 

 

 

 

 

 

 

 

1. Prepare the cable for connection:

PAY

 ATTENTION TO LIVE WIRE

While crimping wires, make sure you clearly 

distinguish the Live (“L”) Wire from other wires.

 

    

7. Insulate unused wires with PVC electrical tape.

    Arrange them so that they do not touch any

    electrical or metal parts.

8. Replace the wire cover on the side of the unit,

    and screw it in place.    

2. Unscrew the electrical wiring cover and remove it.

3. Unscrew the cable clamp below the terminal

    block and place it to the side.

4. Connect the wire according to the wiring 

    diagram, and firmly screw the u-lug of each 

    wire to its corresponding terminal.

5. After checking to make sure every connection is 

    secure, loop the wires around to prevent rain

    water from flowing into the terminal.   

6. Using the cable clamp, fasten the cable to the

    unit. Screw the cable clamp down tightly. 

    

1. Remove the wire cover from the unit by 
    loosening the 3 screws.
2. Dismount caps on the conduit panel.
3. Temperarily mount the conduit tubes(not 
    included) on the conduit panel.
4. Properly connect both the power supply and 
    low voltage lines to the corresponding 
    terminals on the terminal block.
5. Ground the unit in accordance with local codes.
6. Be sure to size each wire allowing several inches
    longer than the required length for wiring.
7. Use lock nuts to secure the conduit tubes.
      

BEFORE PERFORMING ANY ELECTRICAL
OR WIRING WORK, TURN OFF THE MAIN
POWER TO THE SYSTEM.

 WARNING

ALL WIRING WORK MUST BE PERFORMED 
STRICTLY IN ACCORDANCE WITH THE 
WIRING DIAGRAM LOCATED INSIDE OF 
WIRE COVER OF THE OUTDOOR UNIT .

 

 

 

 

 

 

 

 

 

 

 

 

 

In North America

Cover

Screw

Wire Cover 

Over 1.57in.(40mm)

Terminal block

Conduit panel

Connecting cable 

Please select the appropriate through-hole according
to the diameter of the wire.

Three size hole: Small, Large, Medium

When the calbe is not fasten enough, use the
buckle to prop it up , so it can be clamped tightly. 

Buckle        

NOTE: 

If the cable clamp looks like the following,

please select the appropriate through-hole according 
to the diameter of the wire.

 

USE THE RIGHT CABLE 

Please choose the right cable refer to
 “ 

Cable types

” in page 22.

a.  Using wire strippers, strip the rubber 

jacket from both ends of cable to reveal 

about 40mm (1.57in) of the wires inside.

b.  Strip the insulation from the ends of the wires. 

c.  Using a wire crimper, crimp u-lugs on the 

ends of the wires.

CHOOSE THE RIGHT CABLE SIZE

The size of the power supply cable, signal cable, 
fuse, and switch needed is determined by the 
maximum current of the unit. The maximum 
current is indicated on the nameplate located 
on the side panel of the unit.  

NOTE:

 In North America, please choose the right 

cable size according to the Minimum Circuit 
Ampacity indicated on the nameplate of the unit. 

Содержание ICE KLB

Страница 1: ...ng your new air conditioning unit Make sure to save this manual for future reference Please check the applicable models technical data F GAS if any and manufacturer information from the Owner s Manual...

Страница 2: ......

Страница 3: ...Owner s Manual Table of Contents Safety Precautions 03 Care and Maintenance 11 Troubleshooting 13 1 Indoor unit display 07 2 Operating temperature 08 3 Other features 09 4 Setting angle of airflow 10...

Страница 4: ...t 24 Outdoor Unit Installation 25 1 Select installation location 25 2 Install drain joint 26 3 Anchor outdoor unit 26 4 Connect signal and power cables 28 Refrigerant Piping Connection 29 A Note on Pi...

Страница 5: ...rods or other objects into the air inlet or outlet This may cause injury since the fan may be rotating at high speeds Do not use flammable sprays such as hair spray lacquer or paint near the unit Thi...

Страница 6: ...exceeding 30mA and disconnection must be incorporated in the fixed wiring in accordance with the wiring rules For all electrical work follow all local and national wiring standards regulations and th...

Страница 7: ...o not install the unit within 1 meter 3 feet of any combustible materials Do not install the unit in a location that may be exposed to combustible gas leaks If combustible gas accumulates around the u...

Страница 8: ...waste electrical and eletrical equipment should not be mixed with general household waste 2 2 2 2 2 When flammable refrigerant are employed appliance shall be stored in a well ventilated area where t...

Страница 9: ...r On Back of Main Filter Some Units Louver Front Panel when Active Clean feature is turned on For Inverter split type fresh defrost run timer Display window Displays temperature operation feature and...

Страница 10: ...2 F 15 C 24 C 5 F 75 F 0 C 50 C 32 F 122 F 0 C 52 C 32 F 126 F For special tropical models 0 C 52 C 32 F 126 F For special tropical models 15 C 50 C 5 F 122 F For models with low temp cooling systems...

Страница 11: ...professional staff Set temperature 1hr 1hr Keep running SLEEP Operation Saving energy during sleep Heat mode 1 C 2 F per hour for the first two hours Cool mode 1 C 2 F per hour for the first two hour...

Страница 12: ...ecome out of sync If this occurs turn off the unit and unplug it for a few seconds then restart the unit This will reset the louver Range The horizontal angle of the airflow must be set manually Grip...

Страница 13: ...the unit Do not use benzene paint thinner polishing powder or other solvents to clean the unit They can cause the plastic surface to crack or deform Do not use water hotter than 40 C 104 F to clean th...

Страница 14: ...If you plan not to use your air conditioner for an extended period of time do the following Clean all filters Turn on FAN function until unit dries out completely Turn off the unit and disconnect the...

Страница 15: ...Troubleshooting Troubleshooting The unit changes from COOL HEAT mode to FAN mode The indoor unit makes noises A rushing air sound may occur when the louver resets its position A squeaking sound may o...

Страница 16: ...customer service center Provide them with a detailed description of the unit malfunction as well as your model number Troubleshooting Troubleshooting When troubles occur please check the following po...

Страница 17: ...oor heating performance The outdoor temperature is extremely low Use auxiliary heating device Cold air is entering through doors and windows Make sure that all doors and windows are closed during use...

Страница 18: ...Shape Quantity PC Need to be installed on the back of main air filter by the authorized technician while installing the machine Mounting plate fixing screw Remote controller Fixing screw for remote co...

Страница 19: ...g Plate Determine Wall Hole Position 1 2 3 Drill Wall Hole 4 12cm 4 75in 2 3m 90 55in 12cm 4 75in 15cm 5 9in Mount Indoor Unit STEP 8 Wrap Piping and Cable not applicable for some locations in North A...

Страница 20: ...requirement of local and national standards The installation may be slightly different in different areas Wall Mounting Plate Power Cable Some Units Refrigerant Piping Signal Cable Remote Controller...

Страница 21: ...irect sunlight NOTE ABOUT WALL HOLE If there is no fixed refrigerant piping While choosing a location be aware that you should leave ample room for a wall hole see Drill wall hole for connective pipin...

Страница 22: ...When the gas side connective pipe is 16mm 5 8in or more the wall hole should be 90mm 3 54in Left rear wall hole 65mm 2 5in Left rear wall hole 65mm 2 5in Left rear wall hole 65mm 2 5in Left rear wall...

Страница 23: ...extremely careful not to dent or damage the piping while bending them away from the unit Any dents in the piping will affect the unit s performance Step 5 Connect drain hose By default the drain hose...

Страница 24: ...ly resolved 4 Power voltage should be within 90 110 of rated voltage Insufficient power supply can cause malfunction electrical shock or fire 5 If connecting power to fixed wiring a surge protector an...

Страница 25: ...p to fasten the signal cable to the unit Screw the cable clamp down tightly 8 Replace the wire cover on the front of the unit and the plastic panel on the back DRAIN HOSE MUST BE ON BOTTOM Make sure t...

Страница 26: ...pressure to the left and right hand sides of the unit The unit should not jiggle or shift 6 Using even pressure push down on the bottom half of the unit Keep pushing down until the unit snaps onto th...

Страница 27: ...that air outlet fan is at a 90 angle to the direction of the wind If needed build a barrier in front of the unit to protect it from extremely heavy winds See Figures below Strong wind Strong wind Stro...

Страница 28: ...bber seal see Fig B do the following 1 Insert the drain joint into the hole in the base pan of the unit The drain joint will click in place 2 Connect a drain hose extension not included to the drain j...

Страница 29: ...lled holes 5 Remove the nuts from expansion bolts and place outdoor unit on bolts 6 Put washer on each expansion bolt then replace the nuts 7 Using a wrench tighten each nut until snug WARNING WHEN DR...

Страница 30: ...ock 5 Ground the unit in accordance with local codes 6 Be sure to size each wire allowing several inches longer than the required length for wiring 7 Use lock nuts to secure the conduit tubes BEFORE P...

Страница 31: ...This will drastically reduce the heating efficiency of the unit Maximum Length and Drop Height of Refrigerant Piping per Unit Model Refrigerant piping Connection Refrigerant Piping Connection The leng...

Страница 32: ...rs from falling into the pipe 2 Using a reamer or deburring tool remove all burrs from the cut section of the pipe Pipe Reamer Point down Step 3 Flare pipe ends Proper flaring is essential to achieve...

Страница 33: ...0 76 0 78 23 2 23 7 0 91 0 93 18 20 180 200kgf cm 32 39 320 390kgf cm 49 59 490 590kgf cm 57 71 570 710kgf cm 67 101 670 1010kgf cm 9 52 0 375 12 7 0 5 16 0 63 19 0 75 1 Unscrew the cover from the pa...

Страница 34: ...for at least 15 minutes or until the Compound Meter reads 76cmHG 10 Pa 2 3 4 5 5 6 Close the Low Pressure side of the manifold gauge and turn off the vacuum pump 7 Wait for 5 minutes then check that...

Страница 35: ...AUTION DO NOT mix refrigerant types ADDITIONAL REFRIGERANT PER PIPE LENGTH Connective Pipe Length m Air Purging Method Additional Refrigerant Standard pipe length Vacuum Pump N A Standard pipe length...

Страница 36: ...Water Method Using a soft brush apply soapy water or liquid detergent to all pipe connection points on the indoor unit and outdoor unit The presence of bubbles indicates a leak Leak Detector Method If...

Страница 37: ...it will increase This may reveal leaks that were not present during your initial leak check Take time during the Test Run to double check that all refrigerant pipe connection points do not have leaks...

Страница 38: ...ging bag Outdoor Unit 1 Cut the packing belt 2 Take the unit out of the carton 3 Remove the foam from the unit 4 Remove the packaging bag from the unit Packing Indoor unit 1 Put the indoor unit into t...

Страница 39: ......

Страница 40: ...cations are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service website p...

Отзывы: