Replace the compressor
☆
Compressor stuck
R
ef
rig
era
nt
Cir
cuit
Leak test
☆
☆
☆
☆
☆
Shortage of refrigerant
Replace restricted part
☆
☆
☆
Restricted liquid line
Clean or replace
☆
☆
Dirty air filter
Clean coil
☆
☆
Dirty evaporator coil
Check fan
☆
☆
Insufficient air through evaporator coil
Change charged refrigerant volume
☆
☆
☆
☆
☆
Overcharge of refrigerant
Clean condenser or remove obstacle
☆
☆
☆
☆
Dirty or partially blocked condenser
Purge, evacuate and recharge
☆
☆
Air or incompressible gas in refrigerant cycle
Remove obstruction to air flow
☆
☆
Short cycling of condensing air
Remove obstruction in air or water flow
☆
High temperature condensing medium
Remove obstruction in air or water flow
☆
Insufficient condensing medium
Replace compressor
☆
Broken compressor internal parts
Test compressor efficiency
☆
☆
☆
Inefficient compressor
Replace valve
☆
Expansion valve obstructed
Replace valve
☆
☆
Expansion valve or capillary tube closed completely
Replace valve
☆
☆
Leaking power element on expansion valve
Fix feeler bulb
☆
Poor installation of feeler bulb
Check heat load
☆
☆
Heavy load condition
Ot
h
ers
Tighten bolts or screws
☆
Loosen hold down bolts and / or screws
Remove them
☆
Shipping plates remain attached
Choose AC of lager capacity or add the number
of AC
☆
Poor choices of capacity
Rectify piping so as not to contact each other or
with external plate
☆
Contact of piping with other piping or external plate