Displayed code
Explanation
Displayed
value
Meaning
Additional Notes
T1
T
T
T4
Tb
TP
TH
FT
F
Room temperature
-1F,-1E,-1d,-1c,-
1b,-1A
-19
—99
A0,A1,…A9
b0,b1,…b9
c0,c1,…c9
d0,d1,…d9
E0,E1,…E9
F0,F1,…F9
-25,-24,-23,-22,
-21,-20
-19
—99
100,101,…109
110,111,…119
120,121,…129
130,131,…139
140,141,…149
150,151,…159
1. All displayed temperatures
use actual values.
2. All temperatures are
displayed in °C regardless
of remote used.
3. T1, T2, T3, T4, and T2B
display ranges from -25 to
70 °C. TP display ranges
from -20 to 130
°C.
4. The frequency display
ranges from 0 to 159HZ.
5. If the actual values exceed
or fall short of the defined
range, the values closest
to the maximum and
minimum values will be
displayed.
Indoor coil
temperature
Outdoor coil
temperature
Ambient
temperature
Outlet temperature
of indoor coil
Discharge
temperature
Suction temperature
Targeted frequency
Actual frequency
IF
Indoor fan speed
0
1,2,3,4
14-FF
OFF
Low speed, Medium
speed, High speed,
Turbo.
Actual fan speed is
equal to the display
value converted to
decimal value and
multiplied by 10. This
is measured in RPM.
N/A
Used for some large capacity
motors.
Used for some small capacity
motors.
The display value is 14-FF
(hexadecimal). The
corresponding fan speed
ranges from 200 to 2550RPM.
OF
Outdoor fan speed
L
EXV opening angle
0-FF
Actual EXV opening
value is equal to
the display value
converted to decimal
value and then
multiplied by 2.
-
CT
Compressor
continuous running
time
0-FF
0-255 minutes
If the actual value exceeds
or falls short of the defined
range, the value closest to the
maximum and minimum will
be displayed.
T
Causes of
compressor stop
0-99
For a detailed
explanation, contact
technical support.
-
Page 18