background image

6

2.  Setting Date & Time

a.  Use the ‘Up’ and ‘Down’ arrow buttons to set minutes 

(00 to 59).  Press ‘Enter’ to accept new value.

b.  Use the ‘Up’ and ‘Down’ arrow buttons to set hours 

(00 to 23).  Press ‘Enter’ to accept new value.

c.  Use the ‘Up’ and ‘Down’ arrow buttons to set year 

(00 to 99 representing 2000 to 2099).  Press ‘Enter’ to 

accept new value.

d.  Use the ‘Up’ and ‘Down’ arrow buttons to set month 

(three letter abbreviation).  Press ‘Enter’ to accept 

new value.

e.  Use the ‘Up’ and ‘Down’ arrow buttons to set day (01 

to maximum for the month and year selected).  Press 

‘Enter’ to accept new value.

f.  Push ‘ESC’ at any time to return to the Main Menu.

3.  Setting Schedule

a.  Use the ‘Up’ and ‘Down’ arrow buttons to select 

desired “Day of week + on/off”.  Press ‘Enter’ to 

accept new value

b.  Use the ‘Up’ and ‘Down’ arrow buttons to set hour 

(00 to 23).  Press ‘Enter’ to accept new value

 

Note:  If the hour setting is ‘IGNORE’, Press ‘Enter’ 

again to move the cursor under the “Day of week + 

on/off”.  Repeat steps a through b (or c) as needed.

c.  Use the Up and Down arrow buttons to set minutes 

(00, 10, 20, 30, 40, 50; not shown if hour setting is 

‘IGNORE’).  Press ‘Enter’ to accept new value and 

return to “Day of week + on/off”.  Repeat steps a 

through c as needed. 

d.  Push ‘ESC’ at any time to return to the Main Menu.
 

NOTE: Scheduler will ignore programmed commands 

for 10 minutes after exiting program mode.

4.  Hours To Service

a.  Use the ‘Up’ and ‘Down’ arrow buttons to scroll 

through the range of permissible values (0 to 8760) 

before service reminder is initiated.  Press ‘Enter’ 

to accept new value. (Only hours that refrigeration 

compressor is operating are counted).

b.  Press ‘ESC’ at any time to return to the Main Menu.
 

NOTE: On dryers with air-cooled condensers, regular 

condenser cleaning is recommended.  Dirtiness 

of ambient air at installation site will determine 

frequency of service.  Typically once a month is 

recommended.  Dryers contain an integral 3 micron 

filter.  As the filter element accumulates solid 

contaminants, differential pressure increases.  Solid 

particulate load in the compressed air supply will 

determine frequency of service.  Typically element 

changeout is recommended at least annually. 

5.  Push ESC button to exit program mode
 

NOTE: If after 60 seconds no button is pressed while in 

Program Mode, the audible alarm sounds for five (5) 

seconds.  Dryer will resume previous operating mode.

6.  Manual Operation

a.  To manually turn the refrigeration system on or off 

use ‘On/Off’ button; Push ‘Schedule On/Off and 

Enter’ button to return to schedule.

 

NOTE: After power interruption dryer will reenergize 

in Manual override, refrigeration system off. To restart 

Schedule:  Push ‘Schedule On/Off and Enter’ button. 

C.   Starting dryer
IMPORTANT: Dryer must be energized 24 hours before start-

ing refrigeration compressor.
NOTE: It is recommended that dryer be started 15 minutes 

before compressed air flow begins.
1.   On water-cooled models: after 24 hours, begin cooling 

water flow.

2.  Check for proper electrical voltage.
3.  Slowly pressurize unit air side by opening inlet isolation 

valve. Check for leaks.

4.  After 15 minutes, open outlet isolation valve slowly.
5.  Close air bypass valve.
6.  Dryer may be operated in Manual or scheduled modes.
NOTE: CHECK FOR CORRECT PHASING OF UNIT.  After starting 

the dryer, if an unusual noise is heard, or if the discharge 

line does not get hot, the refrigeration compressor may be 

running in the reverse direction.  Immediately stop the dryer, 

reverse two of the power leads, restart the dryer, and verify 

the unusual noise is corrected and the refrigerant discharge 

line is hot.  FAILURE TO DO SO MAY DAMAGE THE COMPRESSOR 

AND VOID THE WARRANTY.
 

Manual mode - push On/Off button - refrigeration 

compressor will start and run, green Compressor-on 

light will illuminate.  In this mode compressor will run 

continuously and will not be turned on and off by the 

monitor. MANUAL OVERRIDE will appear on interface panel. 

 

Schedule mode - push Schedule On/Off and Enter button.  

SCHEDULE RUNNING will appear on the interface panel. 

The refrigeration compressor will continue to be on or off 

(as selected in the Manual Override Mode) until the next 

scheduled event. The compressor will then turn on or off 

as programmed.

NOTE:  Schedule may be returned to the manual mode at any 

time using the ‘Schedule On/Off and Enter’ button. MANUAL 

OVERRIDE will appear on interface panel. To reinstitute 

Schedule, push the ‘Schedule On/Off and Enter’ button again.
NOTE:  Restart after the power interruption. Unit will be in 

MANUAL OVERRIDE mode, refrigeration compressor, off when 

power is restored after power interruption.
7.   To reinstitute SCHEDULE RUNNING, push ‘Schedule On/Off 

and Enter’ button.

IMPORTANT: Dryer must be energized 24 hours before 

refrigeration compressor is started.

D.   Operating check points
1.   Check that green Power-on light is illuminated
2.   Check that green Compressor-on light is illuminated if 

dryer is on in the manual mode or it is a scheduled on 

time. 

IMPORTANT:  Refrigeration compressor must be restarted 

after power interruption.

Содержание TF 171E

Страница 1: ...NG 2 1 0 INSTALLATION 3 2 0 OPERATION 5 3 0 MAINTENANCE 8 SIZING 8 ENGINEERING DATA 9 WIRING DIAGRAM Model TF 171E 10 11 Model TF 210E 12 13 575 460 3 60 Transformer Pack 14 DIMENSIONS WEIGHTS 15 TROU...

Страница 2: ...our plant It was received in good condition by the carrier and was so acknowledged Check for Visible Loss or Damage If this shipment shows evidence of loss or damage at time of delivery to you insist...

Страница 3: ...d 45 to 130 F 7 to 54 C E Installations in altitudes above 4500 feet 1370 meters Dryer is adjusted to operate in altitudes up to 4500 feet 1370 meters If dryer is installed in an altitude above this a...

Страница 4: ...manual draining convenient dryer depressurization and EDD service a three way valve assembly has been installed at the bottom of the moisture separator and cold coalescing filter where applicable Rev...

Страница 5: ...the pilot air supply line and opening the pilot air exhaust line After the pilot air above the diaphragm 4 is vented pressure in the reservoir opens the discharge port and forces the condensate throug...

Страница 6: ...m on or off use On Off button Push Schedule On Off and Enter button to return to schedule NOTE After power interruption dryer will reenergize in Manual override refrigeration system off To restart Sch...

Страница 7: ...contact on the compressor contactor is open when the dryer is off TEMP SENSOR Occurs if the temperature sensor circuit is open or shorted If open the left most LED in the temperature display will be i...

Страница 8: ...tiply the rated capacity from Table 1 by the multipliers shown in Table 2 Example How many scfm can an air cooled model TF 171E handle when compressed air to be dried is at 200 psig and 100 F ambient...

Страница 9: ...psig 9 3 barg Required Available Water Pressure Differential 40 psig 2 8 barg minimum Flow Required with 85 F Cooling Water gallons per minute 60 Hz 4 9 6 8 50 Hz 4 1 5 6 Electrical Data Nominal Volta...

Страница 10: ...only FAN 2 HARNESS FPS 2 FAN 2 REF SHEET 02 LINE 11 REF SHEET 02 LINE 10 REF SHEET 01 LINE 20 03 10 11 12 09 08 07 06 05 04 L3 L3 L3 L2 L2 02 01 00 PE TB1 L1 L2 L3 L1 L1 L1 L2 L3 CONT 1 PE TB2 T1 T2 T...

Страница 11: ...5 W13 W14 W11 W10 W9 W8 W21 W19 Alarm B N C Alarm B Com Drain Test Output Alarm B N O Drain Test Output Compressor 1 Output Compressor 1 Output W27 W18 W17 W16 N A N A W25 W23 FROM SHEET 01 01 03 02 0...

Страница 12: ...HEATER 1 FAN 2 HARNESS FPS 2 FAN 2 REF SHEET 02 LINE 11 REF SHEET 02 LINE 10 REF SHEET 01 LINE 20 03 10 11 12 09 08 07 06 05 04 L3 L3 L3 L2 L2 02 01 00 PE L1 L1 L1 L2 L3 TB1 L1 L3 L2 CONT 1 DISCONNECT...

Страница 13: ...5 W13 W14 W11 W10 W9 W8 W21 W19 Alarm B N C Alarm B Com Drain Test Output Alarm B N O Drain Test Output Compressor 1 Output Compressor 1 Output W27 W18 W17 W16 N A N A W25 W23 FROM SHEET 01 01 03 02 0...

Страница 14: ...14 WIRING DIAGRAM 575 460 3 60 Transformer Pack...

Страница 15: ...25mm ELECTRICAL ENTRY 750 19mm RS 232 ACCESS 0 25 NPT DRAIN CONNECTION MODEL TF171E 0 25 NPT DRAIN CONNECTION MODEL TF210E Dimensions inches mm Model TF 171E TF 210E A 58 06 1475 58 06 1475 B 32 15 81...

Страница 16: ...enser cooling Air cooled Ambient temperature too high clogged condenser fins obstructed flow across condenser faulty fan motor or fan control switch Water cooled Cooling temperature too high flow too...

Страница 17: ...30763 Hot Gas By Pass Valve Air Cooled 5002351 5002351 5002351 5002351 Filter Dryer Liquid Line 5002925 5002925 5002925 5002925 Temperature Sensor 3210926 3210926 3210926 3210926 Contactor 5002926 500...

Страница 18: ...18 NOTES...

Страница 19: ...19...

Страница 20: ...price of the product or part THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER WRITTEN ORAL OR STATUTORY AND IS EXPRESSLY IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABIL...

Отзывы: