IMPORTANT: READ PRIOR TO STARTING THIS EQUIPMENT

1.0 INSTALLATION

1.1  Location  

A.  For typical placement in a compressed air system, see 

drawing.     

B.  Air compressor intake – Locate air compressor so that 

contaminants potentially harmful to the dryer (e.g. 

ammonia) are not drawn into the air system.  

C.  Clearances Free air flow 

Front 36 inches (914 mm)  

 

    

Back 6 inches (152 mm)  

 

    

Sides 36 inches (914 mm)

 

Service - To facilitate maintenance leave 36 inches 

(914 mm) of clearance in front of dryer.

D.  Standard units are designed to operate in ambients: 

Air-cooled: 45 to 110°F (7 to 43°C).   

Water-cooled: 45 to 130°F (7 to 54°C).

E.  Installations in altitudes above 4500 feet (1370 meters) – 

Dryer is adjusted to operate in altitudes up to 4500 feet 

(1370 meters).  If dryer is installed in an altitude above 

this, and has not been preset at the factory for this 

altitude, contact manufacturer’s Service Department.

F.  The installation of a flexible connection prior to the 

dryer is recommended to prevent possible damage from 

vibration.

NOTE: Outdoor installation – Standard units are designed 

for in door installation. Contact manufacturer if installing 

outdoors.

Aftercooler

Separator

Dryer

Oil Removal 

Filter

Compressor

Electric Demand Drain (EDD)

3-Way Valve

Moisture Separator

Coalescing Filter
(Option)

Control Panel

RS232 Entry

Electrical Entry

Air Outlet

Air Inlet

Condenser

Drain Outlet

Содержание TF 171E

Страница 1: ...NG 2 1 0 INSTALLATION 3 2 0 OPERATION 5 3 0 MAINTENANCE 8 SIZING 8 ENGINEERING DATA 9 WIRING DIAGRAM Model TF 171E 10 11 Model TF 210E 12 13 575 460 3 60 Transformer Pack 14 DIMENSIONS WEIGHTS 15 TROU...

Страница 2: ...our plant It was received in good condition by the carrier and was so acknowledged Check for Visible Loss or Damage If this shipment shows evidence of loss or damage at time of delivery to you insist...

Страница 3: ...d 45 to 130 F 7 to 54 C E Installations in altitudes above 4500 feet 1370 meters Dryer is adjusted to operate in altitudes up to 4500 feet 1370 meters If dryer is installed in an altitude above this a...

Страница 4: ...manual draining convenient dryer depressurization and EDD service a three way valve assembly has been installed at the bottom of the moisture separator and cold coalescing filter where applicable Rev...

Страница 5: ...the pilot air supply line and opening the pilot air exhaust line After the pilot air above the diaphragm 4 is vented pressure in the reservoir opens the discharge port and forces the condensate throug...

Страница 6: ...m on or off use On Off button Push Schedule On Off and Enter button to return to schedule NOTE After power interruption dryer will reenergize in Manual override refrigeration system off To restart Sch...

Страница 7: ...contact on the compressor contactor is open when the dryer is off TEMP SENSOR Occurs if the temperature sensor circuit is open or shorted If open the left most LED in the temperature display will be i...

Страница 8: ...tiply the rated capacity from Table 1 by the multipliers shown in Table 2 Example How many scfm can an air cooled model TF 171E handle when compressed air to be dried is at 200 psig and 100 F ambient...

Страница 9: ...psig 9 3 barg Required Available Water Pressure Differential 40 psig 2 8 barg minimum Flow Required with 85 F Cooling Water gallons per minute 60 Hz 4 9 6 8 50 Hz 4 1 5 6 Electrical Data Nominal Volta...

Страница 10: ...only FAN 2 HARNESS FPS 2 FAN 2 REF SHEET 02 LINE 11 REF SHEET 02 LINE 10 REF SHEET 01 LINE 20 03 10 11 12 09 08 07 06 05 04 L3 L3 L3 L2 L2 02 01 00 PE TB1 L1 L2 L3 L1 L1 L1 L2 L3 CONT 1 PE TB2 T1 T2 T...

Страница 11: ...5 W13 W14 W11 W10 W9 W8 W21 W19 Alarm B N C Alarm B Com Drain Test Output Alarm B N O Drain Test Output Compressor 1 Output Compressor 1 Output W27 W18 W17 W16 N A N A W25 W23 FROM SHEET 01 01 03 02 0...

Страница 12: ...HEATER 1 FAN 2 HARNESS FPS 2 FAN 2 REF SHEET 02 LINE 11 REF SHEET 02 LINE 10 REF SHEET 01 LINE 20 03 10 11 12 09 08 07 06 05 04 L3 L3 L3 L2 L2 02 01 00 PE L1 L1 L1 L2 L3 TB1 L1 L3 L2 CONT 1 DISCONNECT...

Страница 13: ...5 W13 W14 W11 W10 W9 W8 W21 W19 Alarm B N C Alarm B Com Drain Test Output Alarm B N O Drain Test Output Compressor 1 Output Compressor 1 Output W27 W18 W17 W16 N A N A W25 W23 FROM SHEET 01 01 03 02 0...

Страница 14: ...14 WIRING DIAGRAM 575 460 3 60 Transformer Pack...

Страница 15: ...25mm ELECTRICAL ENTRY 750 19mm RS 232 ACCESS 0 25 NPT DRAIN CONNECTION MODEL TF171E 0 25 NPT DRAIN CONNECTION MODEL TF210E Dimensions inches mm Model TF 171E TF 210E A 58 06 1475 58 06 1475 B 32 15 81...

Страница 16: ...enser cooling Air cooled Ambient temperature too high clogged condenser fins obstructed flow across condenser faulty fan motor or fan control switch Water cooled Cooling temperature too high flow too...