background image

16

TROUBLESHOOTING GUIDE

SYMPTOM

POSSIBLE CAUSE(S)

CORRECTIVE ACTION

A)  Water downstream of dryer

1.  Residual free moisture remaining in 

downstream pipelines

2.  Air bypass system is open

3.  Inlet and Outlet connections are reversed

4.  Air lines downstream of dryer are exposed 

to temperatures below the dew point.

5.  Excessive free moisture (bulk liquid) at 

dryer inlet.

6.  Condensate not being drained  

7.  Dryer overloaded resulting in elevated 

dew point.

8.  Refrigeration system not functioning 

1.  Blow out system with dry air

2.  Check valve positions

3.  Check for correct connection

4.  Insulate or heat trace air lines exposed to 

low ambients or dry air to lower dew point

5.  Install separator ahead of dryer

6.  See C below

7.  See C below

8.  See C below

B)  High pressure drop across dryer

1.  Excessive air flow

2.  Freezing of moisture in evaporator 

because of refrigeration system fault

3.  Filter loaded with solid particulates 

1.  Check flow rate

2.  See C below

3.  Replace filter element

C)  Checkpoint faults

1.   Power on light off

2.  Compressor on light off 

 

3.  Alarm/Service alert light on 

-check Display for active 

conditions

SERVICE DRYER

  

LOW PRESSURE

  

HIGH PRESSURE

NOTE: If high refrigerant pressure 

occurs, switch must be manually 

reset  

 

  

HIGH TEMPERATURE

(also observed as high reading on 

temperature indicator)

  

DRAIN

 

COMPRESSOR

HEATER

TEMP SENSOR

a.  Power failure; open circuit 

a.  Compressor commanded off by manual 

switch or programmed schedule

b.  Open circuit

c.  Control circuit open on high or low 

pressure cutout

a.  Service interval specified has elapsed

a.  Hot gas bypass valve requires adjustment

b.  Low on refrigerant

a.  Lack of condenser cooling 

 

Air-cooled - Ambient temperature too 

high, clogged condenser fins, obstructed 

flow across condenser, faulty fan motor or 

fan control switch.

 

Water-cooled - Cooling temperature too 

high, flow too low, clogged strainer, faulty 

water regulating valve  

a.  Dryer overloaded

b.  Refrigeration system off or not cooling 

sufficiently

a.  Drain line restricted or frozen

b.  Drain mechanism faulty

a.  Faulty compressor contactor.

b.  Faulty N.O. auxiliary contact on 

compressor contactor.

a.  Faulty compressor contactor.

b.  Faulty N.C. auxiliary contact on 

compressor contactor.

a.  Temperature sensor or wiring to sensor 

is open (only the left-most LED in the 

temperature display will be illuminated).

b.  Temperature sensor or wiring to sensor is 

shorted (all of the LEDs in the temperature 

display will be illuminated).

a.  Check for power to dryer

a.  Check current command status

b.  Check power to compressor

c.  Check display for fault

a.  Perform scheduled service

a.  Contact qualified technician or 

manufacturer’s service department

 

Check air temperature 6” in front of 

condenser;  Clean condenser and check 

for free air flow; Check fan and switch 

operation

 

Check cooling medium temperature and 

flow, clean strainer, check valve operation

a.  Check compressed air flow, temperature, 

and pressure

b.  Check power to unit, power to 

compressor, Low or High pressure faults 

Have qualified technician evaluate system 

a.  Open drain line

b.  Turn 3-way valve to horizontal position 

and open petcock for manual draining. 

Rebuild drain mechanism.

a.  Check wiring and operation of contactor.

b.  Check wiring and operation of auxiliary 

contact.

a.  Check wiring and operation of contactor.

b.  Check wiring and operation of auxiliary 

contact.

a.  Replace sensor or repair wiring.

b.  Replace sensor or repair wiring.

NOTE:  After fault correction, press reset button to clear display

Содержание TF 171E

Страница 1: ...NG 2 1 0 INSTALLATION 3 2 0 OPERATION 5 3 0 MAINTENANCE 8 SIZING 8 ENGINEERING DATA 9 WIRING DIAGRAM Model TF 171E 10 11 Model TF 210E 12 13 575 460 3 60 Transformer Pack 14 DIMENSIONS WEIGHTS 15 TROU...

Страница 2: ...our plant It was received in good condition by the carrier and was so acknowledged Check for Visible Loss or Damage If this shipment shows evidence of loss or damage at time of delivery to you insist...

Страница 3: ...d 45 to 130 F 7 to 54 C E Installations in altitudes above 4500 feet 1370 meters Dryer is adjusted to operate in altitudes up to 4500 feet 1370 meters If dryer is installed in an altitude above this a...

Страница 4: ...manual draining convenient dryer depressurization and EDD service a three way valve assembly has been installed at the bottom of the moisture separator and cold coalescing filter where applicable Rev...

Страница 5: ...the pilot air supply line and opening the pilot air exhaust line After the pilot air above the diaphragm 4 is vented pressure in the reservoir opens the discharge port and forces the condensate throug...

Страница 6: ...m on or off use On Off button Push Schedule On Off and Enter button to return to schedule NOTE After power interruption dryer will reenergize in Manual override refrigeration system off To restart Sch...

Страница 7: ...contact on the compressor contactor is open when the dryer is off TEMP SENSOR Occurs if the temperature sensor circuit is open or shorted If open the left most LED in the temperature display will be i...

Страница 8: ...tiply the rated capacity from Table 1 by the multipliers shown in Table 2 Example How many scfm can an air cooled model TF 171E handle when compressed air to be dried is at 200 psig and 100 F ambient...

Страница 9: ...psig 9 3 barg Required Available Water Pressure Differential 40 psig 2 8 barg minimum Flow Required with 85 F Cooling Water gallons per minute 60 Hz 4 9 6 8 50 Hz 4 1 5 6 Electrical Data Nominal Volta...

Страница 10: ...only FAN 2 HARNESS FPS 2 FAN 2 REF SHEET 02 LINE 11 REF SHEET 02 LINE 10 REF SHEET 01 LINE 20 03 10 11 12 09 08 07 06 05 04 L3 L3 L3 L2 L2 02 01 00 PE TB1 L1 L2 L3 L1 L1 L1 L2 L3 CONT 1 PE TB2 T1 T2 T...

Страница 11: ...5 W13 W14 W11 W10 W9 W8 W21 W19 Alarm B N C Alarm B Com Drain Test Output Alarm B N O Drain Test Output Compressor 1 Output Compressor 1 Output W27 W18 W17 W16 N A N A W25 W23 FROM SHEET 01 01 03 02 0...

Страница 12: ...HEATER 1 FAN 2 HARNESS FPS 2 FAN 2 REF SHEET 02 LINE 11 REF SHEET 02 LINE 10 REF SHEET 01 LINE 20 03 10 11 12 09 08 07 06 05 04 L3 L3 L3 L2 L2 02 01 00 PE L1 L1 L1 L2 L3 TB1 L1 L3 L2 CONT 1 DISCONNECT...

Страница 13: ...5 W13 W14 W11 W10 W9 W8 W21 W19 Alarm B N C Alarm B Com Drain Test Output Alarm B N O Drain Test Output Compressor 1 Output Compressor 1 Output W27 W18 W17 W16 N A N A W25 W23 FROM SHEET 01 01 03 02 0...

Страница 14: ...14 WIRING DIAGRAM 575 460 3 60 Transformer Pack...

Страница 15: ...25mm ELECTRICAL ENTRY 750 19mm RS 232 ACCESS 0 25 NPT DRAIN CONNECTION MODEL TF171E 0 25 NPT DRAIN CONNECTION MODEL TF210E Dimensions inches mm Model TF 171E TF 210E A 58 06 1475 58 06 1475 B 32 15 81...

Страница 16: ...enser cooling Air cooled Ambient temperature too high clogged condenser fins obstructed flow across condenser faulty fan motor or fan control switch Water cooled Cooling temperature too high flow too...

Страница 17: ...30763 Hot Gas By Pass Valve Air Cooled 5002351 5002351 5002351 5002351 Filter Dryer Liquid Line 5002925 5002925 5002925 5002925 Temperature Sensor 3210926 3210926 3210926 3210926 Contactor 5002926 500...

Страница 18: ...18 NOTES...

Страница 19: ...19...

Страница 20: ...price of the product or part THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER WRITTEN ORAL OR STATUTORY AND IS EXPRESSLY IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABIL...

Отзывы: