background image

4

1.2   Mounting 

Mount on floor or shelf free from vibration.

1.3   Piping connections 

A.  Air Inlet - Connect compressed air line from air source 

to air inlet.  (Reference markings on dryer or see callout 

drawing on page 14 for air inlet/outlet connection 

locations.)

   

Refer to Serial Number Tag for maximum 

working pressure.  Do not exceed dryer’s Maximum Working 

Pressure.
NOTE:  Install dryer in air system at highest pressure possible 

(e.g. before pressure reducing valves).
NOTE:  Install dryer at coolest compressed air temperature 

possible.  Maximum inlet compressed air temperature: 120°F 

(49°C).  If inlet air exceeds this temperature, precool the air 

with an aftercooler.  
B.  Air Outlet – Connect air outlet to downstream air lines.
C.  Bypass piping – If servicing the dryer without interrupting 

the air supply is desired, piping should include inlet and 

outlet valves and an air bypass valve.

D.  Water cooled models – cooling water inlet and outlet

1.  Connect cooling water supply to cooling water inlet.

2.  Connect cooling water return line to cooling water 

outlet connection.

NOTE:  Strainer and water regulating valve are supplied on 

water cooled models.

1.4   Electrical connections

IMPORTANT:  Use copper supply wires only.
A.  Dryer is designed to operate on the 

voltage, phase, and frequency listed on 

the serial number tag.

B.  Connect power source to terminal strip in electrical 

enclosure.

NOTE:  Refrigeration condensing unit is designed to run 

continuously and should NOT be wired to cycle on/off with 

the air compressor.
NOTE: CHECK FOR CORRECT PHASING OF UNIT.  After starting 

the dryer, if an unusual noise is heard, or if the discharge 

line does not get hot, the refrigeration compressor may be 

running in the reverse direction.  Immediately stop the dryer, 

reverse two of the power leads, restart the dryer, and verify 

the unusual noise is corrected and the refrigerant discharge 

line is hot.  FAILURE TO DO SO MAY DAMAGE THE COMPRESSOR 

AND VOID THE WARRANTY.

1.5   Moisture separator 

A.    An automatic electric demand drain (EDD) 

discharges condensate removed by the 

separator.  It may be desirable to pipe 

the condensate from the EDD outlet to a 

suitable drain.

B.    For manual draining, convenient dryer depressurization, 

and EDD service, a three-way valve assembly has been 

installed at the bottom of the moisture separator (and 

cold coalescing filter where applicable).  Review the 

following for proper drain function:
•  Automatic Draining - Valve handle should be 

positioned parallel to the valve body (as shown), with 

the arrow on the handle pointing toward the EDD.  In 

this position, condensate will flow from the bowl to 

the EDD.

•  Drain Isolation (Shutdown) - Valve handle shall be 

turned perpendicular to the valve body (rotate 90°).  In 

this position, condensate flow is shutoff.

 

•  Manual Draining - Drain valve handle shall be rotated 

slightly past the drain isolation position to allow 

throttling through the valve for manual discharge and 

depressurization.

•  NOTE:  The quick disconnect fitting allows removal of 

the entire drain assembly.  

However, the unit must 

be depressurized prior to disassembly or serious 

injury may occur.

NOTE:  Discharge is at system pressure. Drain line should be 

anchored.
NOTE:  Condensate may contain oil. Comply with applicable 

laws concerning proper disposal.

1.6 Operation

A.  Verify that isolation valves are open. If the drain fails to 

discharge after the valve is energized, the electronic 

control circuit will repeatedly energize the valve in an 

attempt to clear the discharge port.  If, after 60 seconds, 

the drain still fails to discharge, the control circuit then 

switches to the alarm mode.  In this mode the valve 

is de-energized and the red alarm light is activated on 

the drain and the dryer controller. The valve is then 

automatically energized every 4 minutes for 5 seconds.  

Check the drain operation.  Push drain (push-to-test) 

button on the Energy Management Monitor control 

board to energize drain.  A flow of condensate and/or air 

should be present at the drain outlet.  The alarm mode 

automatically clears after the drain returns to normal 

operation.

B.  Condensate enters the reservoir 

(1)

 through the inlet 

port. When the condensate level in the reservoir covers 

the capacitance sensor, an electronic signal is sent to the 

solid state countdown processor.  The processor delays 

the opening of the solenoid valve for a given period 

of time.  Once the time has elapsed, the solid state 

processor transmits information to energize the coil in 

the solenoid valve 

(2)

.  The magnetic force of the coil 

Содержание TF 171E

Страница 1: ...NG 2 1 0 INSTALLATION 3 2 0 OPERATION 5 3 0 MAINTENANCE 8 SIZING 8 ENGINEERING DATA 9 WIRING DIAGRAM Model TF 171E 10 11 Model TF 210E 12 13 575 460 3 60 Transformer Pack 14 DIMENSIONS WEIGHTS 15 TROU...

Страница 2: ...our plant It was received in good condition by the carrier and was so acknowledged Check for Visible Loss or Damage If this shipment shows evidence of loss or damage at time of delivery to you insist...

Страница 3: ...d 45 to 130 F 7 to 54 C E Installations in altitudes above 4500 feet 1370 meters Dryer is adjusted to operate in altitudes up to 4500 feet 1370 meters If dryer is installed in an altitude above this a...

Страница 4: ...manual draining convenient dryer depressurization and EDD service a three way valve assembly has been installed at the bottom of the moisture separator and cold coalescing filter where applicable Rev...

Страница 5: ...the pilot air supply line and opening the pilot air exhaust line After the pilot air above the diaphragm 4 is vented pressure in the reservoir opens the discharge port and forces the condensate throug...

Страница 6: ...m on or off use On Off button Push Schedule On Off and Enter button to return to schedule NOTE After power interruption dryer will reenergize in Manual override refrigeration system off To restart Sch...

Страница 7: ...contact on the compressor contactor is open when the dryer is off TEMP SENSOR Occurs if the temperature sensor circuit is open or shorted If open the left most LED in the temperature display will be i...

Страница 8: ...tiply the rated capacity from Table 1 by the multipliers shown in Table 2 Example How many scfm can an air cooled model TF 171E handle when compressed air to be dried is at 200 psig and 100 F ambient...

Страница 9: ...psig 9 3 barg Required Available Water Pressure Differential 40 psig 2 8 barg minimum Flow Required with 85 F Cooling Water gallons per minute 60 Hz 4 9 6 8 50 Hz 4 1 5 6 Electrical Data Nominal Volta...

Страница 10: ...only FAN 2 HARNESS FPS 2 FAN 2 REF SHEET 02 LINE 11 REF SHEET 02 LINE 10 REF SHEET 01 LINE 20 03 10 11 12 09 08 07 06 05 04 L3 L3 L3 L2 L2 02 01 00 PE TB1 L1 L2 L3 L1 L1 L1 L2 L3 CONT 1 PE TB2 T1 T2 T...

Страница 11: ...5 W13 W14 W11 W10 W9 W8 W21 W19 Alarm B N C Alarm B Com Drain Test Output Alarm B N O Drain Test Output Compressor 1 Output Compressor 1 Output W27 W18 W17 W16 N A N A W25 W23 FROM SHEET 01 01 03 02 0...

Страница 12: ...HEATER 1 FAN 2 HARNESS FPS 2 FAN 2 REF SHEET 02 LINE 11 REF SHEET 02 LINE 10 REF SHEET 01 LINE 20 03 10 11 12 09 08 07 06 05 04 L3 L3 L3 L2 L2 02 01 00 PE L1 L1 L1 L2 L3 TB1 L1 L3 L2 CONT 1 DISCONNECT...

Страница 13: ...5 W13 W14 W11 W10 W9 W8 W21 W19 Alarm B N C Alarm B Com Drain Test Output Alarm B N O Drain Test Output Compressor 1 Output Compressor 1 Output W27 W18 W17 W16 N A N A W25 W23 FROM SHEET 01 01 03 02 0...

Страница 14: ...14 WIRING DIAGRAM 575 460 3 60 Transformer Pack...

Страница 15: ...25mm ELECTRICAL ENTRY 750 19mm RS 232 ACCESS 0 25 NPT DRAIN CONNECTION MODEL TF171E 0 25 NPT DRAIN CONNECTION MODEL TF210E Dimensions inches mm Model TF 171E TF 210E A 58 06 1475 58 06 1475 B 32 15 81...

Страница 16: ...enser cooling Air cooled Ambient temperature too high clogged condenser fins obstructed flow across condenser faulty fan motor or fan control switch Water cooled Cooling temperature too high flow too...

Страница 17: ...30763 Hot Gas By Pass Valve Air Cooled 5002351 5002351 5002351 5002351 Filter Dryer Liquid Line 5002925 5002925 5002925 5002925 Temperature Sensor 3210926 3210926 3210926 3210926 Contactor 5002926 500...

Страница 18: ...18 NOTES...

Страница 19: ...19...

Страница 20: ...price of the product or part THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER WRITTEN ORAL OR STATUTORY AND IS EXPRESSLY IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABIL...

Отзывы: