Direct online starting
Star-delta starting
EPC type Current input
[A]
Backup fuse
[A]
Supply cable
[mm
2
]
Backup fuse
[A]
Supply cable
[mm
2
]
1000-2-G
10.4
●
20
4 x 2.5
–
–
● Pressure switch
○ Controller (star-delta)
Tab. 19 Supply details 690V/3/50Hz
Mains frequency: 60 Hz
Rated voltage: 230V±10%/3/60Hz
Direct online starting
Star-delta starting
EPC type Current input
[A]
Backup fuse
[A]
Supply cable
[mm
2
]
Backup fuse
[A]
Supply cable
[mm
2
]
150-2-G
4.6
●
10
4 x 1.5
–
–
230-2-G
6.9
●
16
4 x 2.5
–
–
420-2-G
10.9
●
20
4 x 2.5
16
4 x 2.5
550-2-G
17.4
○
35
4 x 6
20
4 x 2.5
750-2-G
21.0
○
50
4 x 10
25
4 x 4
1000-2-G
28.0
○
63
4 x 16
35
4 x 6
● Pressure switch
○ Controller (star-delta)
Tab. 20 Supply details 230V/3/60Hz
Rated voltage: 380V±10%/3/60Hz
Direct online starting
Star-delta starting
EPC type Current input
[A]
Backup fuse
[A]
Supply cable
[mm
2
]
Backup fuse
[A]
Supply cable
[mm
2
]
150-2-G
2.8
●
6
4 x 1.5
–
–
230-2-G
4.2
●
10
4 x 1.5
–
–
420-2-G
7.1
●
16
4 x 2.5
10
4 x 1.5
550-2-G
10.5
●
20
4 x 2.5
16
4 x 2.5
750-2-G
12.5
●
25
4 x 4
16
4 x 2.5
1000-2-G
19.0
○
35
4 x 6
20
4 x 2.5
● Pressure switch
○ Controller (star-delta)
Tab. 21 Supply details 380V/3/60Hz
2
Technical Specification
2.11 Power Supply
10
Assembly and operating manual 2-stage piston compressor
EPC-2-G
No.: 9_5753_04 E
Содержание EPC 1000-2-G