10.4.2.1 Parameter for power ramp

4

1

2

3

4

Power ramp

NOTE: The power ramp allows a moderate increase of the Perform-
ance possible

Gradient

 1 – 600 [% / min]

Gradient of power limit. The maximum power limit increase to 100% of
nominal power with the gradient specified.

After every connect

Soft start ramp up is activated for every connection of the inverter to
the grid

After first connect

Soft start ramp up is activated for the first connection of the inverter to
the grid on a particular day or after complete reboot of the inverter (AC
and DC disconnected)

After grid error

Soft start ramp up is activated for connection of the inverter to the grid
after trip of the internal interface protection or via the external grid pro-
tection port (Powador-protect)

10.5

Advanced islanding detection

Due to decentralized generation, there is the possibility that a deactivated part of the grid will remain live in an uninten-
ded island due to the balance of load and generation in this part of the grid. The detection of unintended island formation
is an important function of decentralized generating units and is related to the prevention of damage to equipment as
well as safety of personnel.

Depending on the structure and the operation of the distribution grid several dangers exist:

ž

In case of maintenance work in a distribution grid, personnel may be placed in danger if the deactivated part of the
grid remains live as an island. This is especially the case if not all safety rules are followed.

ž

If fast auto-reclosure is used in a distribution grid and the deactivated part of the grid remains live as an island, reclos-
ure will likely happen during phase displacement which might cause damage to rotating machinery on the grid.

ž

In the event of a fault in a medium voltage grid, the faulty part of the grid is disconnected. If the fault has a significant
resistance, the deactivated part of a medium-voltage grid remains live as an island. Depending on the type of fault, but
explicitly in case of a fault in the transformer, dangerous medium voltage might be accessible or even present in low-
voltage appliances.

Especially for the last example very fast disconnection of the generating units to cause collapse of the forming island is
necessary. At the same time any island formation detection method may cause false tripping. The industry is therefore in
constant research to develop methods that are fast and reliable and at the same time reliably prevent false tripping.

Enhanced island detection method

The enhanced island detection of KACO new energy, employs a strategy to reliably detect island formation that is based
on the characteristic differences between an interconnected grid and an islanded grid, thus ensuring reliable fast detec-
tion and prevention of false tripping.

An interconnected grid is dominated by rotating machinery, as a consequence frequency is proportional to active power
balance and voltage is proportional to reactive power balance. In contrast an islanded grid behaves like a resonant circuit,
as a consequence frequency is proportional to reactive power balance and voltage is proportional to active power bal-
ance. The active enhanced island detection method detects this difference by monitoring the behaviour of the grid. The
enhanced island detection is monitoring the natural fluctuation of the grid frequency and injects a minimal reactive
power proportional to the rate of change of frequency. In the moment of formation of an island the connected power
systems is closing a positive feedback loop what allows the inverter to detect the changed situation and to disconnect. In
case of formation of an island, the inverter disconnects within some 100 ms, well below 1000 ms.

ž

The number of parallel inverters does not affect the reliability of this function.

ž

This method also ensures that the impact on the distribution grid is kept to a minimum.

ž

In normal operation no effects on harmonic content, flicker and grid stability are detected.

This detection method is combined with a two stage passive rate of change of frequency (ROCOF) observation. If the RO-
COF of the grid exceeds the configured disconnection threshold (stage 1) for the configured disconnection time, the
device switches to zero current mode. If the ROCOF of the grid exceeds the configured shutdown threshold (stage 2) for

KACO blueplanet gridsave 50.0TL3-S

Page 68

EN

Содержание blueplanet gridsave 50.0TL3-S Series

Страница 1: ...l Basic M L XL KACO blueplanet gridsave 50 0TL3 S These instructions form part of the product and must be carefully read observed and stored in a place which is freely accessible at all times Authoris...

Страница 2: ...conditions contact your system integrator Definitions on product designations In these operating instructions the product Bidirectional feed in inverter is referred to as device for ease of reading T...

Страница 3: ...5 7 7 Connecting the interfaces 25 7 8 Sealing the connection area 28 8 Commissioning 29 8 1 Requirements 29 9 Configuration and operation 30 9 1 Initial start up 30 9 2 Controls 30 9 3 Menu structure...

Страница 4: ...ion KACO art no blueplanet gs 50 0TL3 S B1 WM OD IIGB 1001742 blueplanet gs 50 0TL3 S B1 WM OD IIGM 1001743 blueplanet gs 50 0TL3 S B1 WM OD IIGL 1001732 blueplanet gs 50 0TL3 S B1 WM OD IIGX 1001741...

Страница 5: ...5678 Year Q3 19 Input DC U max I max 1050 V 90 A U operation range 662 V 1050 V Output Nominal voltage 230 V 400 V 3 N PE 220 V 380 V 3 N PE Voltage range continuous operation 165 V 288 V Ph N Current...

Страница 6: ...ion of electrical devices and systems Education concerning the installation and start up of electrical devices and systems Knowledge of applicable standards and directives Knowledge and adherence to t...

Страница 7: ...tructions on the product and in these operating instructions Switch off all voltage sources and secure them against being inadvertently switched back on before performing visual inspections and mainte...

Страница 8: ...itoring system EMC filter to protect the inverter from high frequency grid interference Grid side varistors grounded to earth to protect the product against burst and surge pulses Anti islanding detec...

Страница 9: ...ation period 23 days the device disconnects from the grid at midnight and performs a restart in cluding a self test 3 2 Device diagram 5 6 7 1 4 8 2 3 Fig 3 Device diagram 1 Housing 5 DC connection ca...

Страница 10: ...ware updates using a FAT32 formatted USB stick 3 3 System layout Battery with management system Bidirectional feed in inverter with interface switch Line protection DC isolator switch Grid DC fuse Fig...

Страница 11: ...ls AC Nominal power 50 0 kVA 220V 50 0 kVA 230V Rated voltage 230 400 V 3 N PE 220 V 380 V 3 N PE Voltage range continuous operation 165 V 288 V PH N Rated current 3 x 72 2 A 400V 3 x 76 0 A 380V Max...

Страница 12: ...ator switch no AC isolator switch no Cooling temp regulated fan max air throughput 218 m h per fan Max power dissipation to room air 2 1 5 kW Number of fans 2 Noise emission 61 db A Housing material A...

Страница 13: ...hin six days following receipt of the device We will be glad to help you if necessary 5 2 Transporting the device CAUTION Hazard due to impact risk of breakage to the device Pack the device securely f...

Страница 14: ...nnector W External hexagon A Internal hexagon T Torx S Slot Tab 1 Key and description of tool codes Outer contour Tightening torque Spanner size or number Nm Fig 6 Form pattern KACO blueplanet gridsav...

Страница 15: ...ally on vents Failure to observe these warnings may lead to device damage which is not covered by the manufac turer warranty NOTE Access by maintenance personnel for service Any additional costs arisi...

Страница 16: ...mbly can result in injuries e g back injuries Only lift the device using the openings provided The device must be transported and installed by at least 2 persons DETAILZ4 1 Z 2 1 3 4 5 6 Fig 9 Open th...

Страница 17: ...ws for mounting 5x SW 13 Fastening the mount See section 6 3 Page 17 8 Seating recess A Minimum clearance 120 mm without device370 mm recommended distance400 mm without device 550 mm C Minimum clearan...

Страница 18: ...device using the opening N O 5 4 Fig 14 Insertion aid in mount Key 1 Opening 4 Marking for insertion into mount 2 Centre of gravity 5 Outer contour of the mount 3 Warning sign attachment prohibited Li...

Страница 19: ...vice during installation and start up Keep the device closed during pre assembly and do not open the connection area until you perform in stallation Seal off the screw connections using sealing covers...

Страница 20: ...e to the fact that the device is unable to limit the short circuit current from the grid in the event of a short circuit the AC side fuse in the installation on site provides protection against faults...

Страница 21: ...ew terminal PE bolt Ground conductor connection M8 Fuse protection for installation provided by customer min 100 A max 125 A Fitting for AC connection M63 Cable diameter for cable fitting 32 42 mm Tab...

Страница 22: ...ing of the AC cables 3 Insert the AC cables through the cable fitting into the connection area 4 Strip the AC lines approx 25 mm Make the grid connection DC side AC side Fig 16 Terminals 7 4 2 Make th...

Страница 23: ...D IIGL Blueplanet gs 50 0TL3 S B1 WM OD IIGX Connection cable with 2 x 1 strands already on the device 1 Unfasten the protective cover using the 4 screws and place to one side T15 2 Unscrew the cable...

Страница 24: ...2 x 1 strands already on the device 1 Unscrew the cable fitting W_ws 36 2 Remove the outer cladding of the DC cables 3 Pass the DC cables through the cable fittings into the connection compartment 4...

Страница 25: ...screws T15 2 3 Nm 12Tighten the cable fittings W_ws 36 5 Nm M8 M8 20 mm DC DC Fig 21 DC connection B version 7 6 Creating equipotential bonding The device has been installed on the mount 1 Strip the...

Страница 26: ...powador protect 3 USB Connection for update 7 7 2 Insert and lay the cables DANGER Risk of fatal injury due to electric shock Touching damaged insulation on the grid and battery connection leads resul...

Страница 27: ...g the Ethernet cable Connecting cable inside the device 1 Plug in an Ethernet cable at one of the two Ethernet ports on the communication circuit board 2 Check that the connecting cable is fitted secu...

Страница 28: ...e the support for Powador protect in the para meter menu under the Powador protect menu option D01 GND 4 3 2 1 INV Signal RS485 GND GND INV OFF 1 2 x x y y BA BA RS485 GND GND INV OFF BA BA Powador pr...

Страница 29: ...surface Heat sinks become very hot when in operation Never touch the heat sinks after commissioning the device Allow the heat sinks at least 10 minutes to cool down before cleaning The device has been...

Страница 30: ...me 4 To store the set operator country and grid type permanently confirm with Yes You have completed the initial configuration The device begins operation 9 2 Controls The device has a backlit LCD dis...

Страница 31: ...ss the right arrow button The menu moves over the desktop from left to right Displaying the daily output The device is in operation and the LCD is showing the desktop F Press the down arrow button The...

Страница 32: ...easurements of the battery Charge status SoC Service life SoH Temperature C 4 1 2 3 4 Grid Displays the AC side voltage amperage and power 4 1 2 3 4 cos phi Displays the reactive power factor cos of t...

Страница 33: ...Enter button 4 1 2 3 4 Decimal separator F Select decimal sign for export of saved operating data 4 1 2 3 4 Save to USB NOTE Opportunity to export the operating data to a connected USB storage device...

Страница 34: ...ime without user input after which the backlight ing of the LCD switches off 3 Alternatively Permanently activate or disable the backlighting by selecting On or Off 4 1 2 3 4 Date time NOTE For self d...

Страница 35: ...ay the Parameters menu in the standard configuration To display the Parameters menu 1 Open the menu 2 Simultaneously hold down the Up and Down buttons for sev eral seconds 4 1 2 3 4 Country NOTE This...

Страница 36: ...id voltage exceeds or drops below the configured values the device switches off The minimum switch off threshold can be set in 1 Volt increments 1 Configure the switch off values for undervoltage and...

Страница 37: ...ce 4 1 2 3 4 Check surge protection device NOTE Please refer to the application note on our website if you install the overvoltage protection yourself NOTE Allows the monitoring of the overvoltage pro...

Страница 38: ...h F Further parameterisation is possible via the web interface 4 1 2 3 4 Reactive power 1 Open the menu Press the Right arrow button or Enter button 2 Activating reactive power process Select process...

Страница 39: ...l is ac tivated 4 1 2 3 4 Lock out power 0 100 Smax F Set the active power as of rated power below which control is de activated 4 1 2 3 4 Lock in time 0 s 60 s F Set the length of time that the activ...

Страница 40: ...10th node Voltage Reactive power Excitation 0 max voltage in continuous operation F Enter the voltage of the node in volts 0 100 Smax F Set the reactive power of the node as a percentage of the maxim...

Страница 41: ...ly in ac cordance with the country specific GridCode F Apply the settings in accordance with the specifications of the sys tem integrator 4 1 2 3 4 Iso resistor F Set threshold value in 1kOhm incremen...

Страница 42: ...de 1 Mode 2 F Select dead band mode for the active control process 4 1 2 3 4 Reference voltage U U F Set reference voltage for the active control process 4 1 2 3 4 Minimum operating voltage 45 125 0 U...

Страница 43: ...Activate active grid influence by additional reactive power feed in 4 1 2 3 4 Frequency shift Off On F Activate frequency shift 4 1 2 3 4 Pulse period repetition time 40 6000 ms F Define period for de...

Страница 44: ...parent power is limited globally to the configured value in VA All active and reactive power control values use Slim instead of Smax as 100 if Slim is configured 4 1 2 3 4 Maximum active power Plim 1...

Страница 45: ...o an inductive load 0 100 Unom F Enter the voltage of the node in volts NOTE The voltage values of the nodes must increase continuously At voltages below the 1st node and voltages above the last node...

Страница 46: ...2 3 4 Dynamic gradient mode On Off F Activate dynamic gradient 4 1 2 3 4 Maximum dynamic gradient frequency 50 22 70 5 Hz Minimum dynamic gradient frequency 45 50 Hz F Specify dynamic gradient freque...

Страница 47: ...adient limitation de crease 1 65534 min F Specify the increasing and decreasing output gradient 4 1 2 3 4 Active curve 1 5 F Select active curve NOTE Up to 5 characteristic curves can be configured in...

Страница 48: ...rtificates are only valid if the corresponding country settings have been selected that all configured grid parameters must be configured in accordance with the requirements of the grid operators that...

Страница 49: ...oltage Grid power Unit temperature Grid voltage Tab 5 Measurement data display In order to display and export yield data proceed as follows Select the display period 1 Call up the web server 2 Select...

Страница 50: ...ay In this case select No and perform the update with a stable power supply Performing a firmware update Ensure that the power supply is connected 1 Connect the USB stick to the device The message app...

Страница 51: ...llowing figures show the reactive power active power operating range for devices with a nominal voltage of UN 220 380 230 400 240 415 Voltage devices with UN 220 V 380 V 230 V 400 V 240 V 415 V Maximu...

Страница 52: ...oller Q constant When there is a Q constant the specified reactive power value is set permanently by the inverter If the specification is changed the new value is adopted by way of a filter in a muted...

Страница 53: ...ment factor Over excited un der excited Reactive power mode Under excited relates to inductive load over ex cited relates to capacitive load Q constant 0 100 Smax Specification as a of the maximum pow...

Страница 54: ...reactive power setting can be determined by a maximum gradient this means the maximum change in the reactive power per time period 1 60000 Smax min Maximum change in the reactive power SN min in the...

Страница 55: ...y increase The function P f is available for this purpose However depending on the selected country setting the availability or adjustability of the functions may be limited This is particularly the c...

Страница 56: ...en a target value is received for P limit the output power of the inverter is limited to the specified power value If the limit value is changed the new value is adopted by way of a filter and a gradi...

Страница 57: ...ocess you should also check whether internal and or external power reduction is active Internal power limitation Parameters for external power limita tion Parameters for power limitation Status active...

Страница 58: ...time increases above the abso lute power limit See figure 35 Page 58 and See figure 36 Page 58 are two examples of configuration In figure 1 without hys teresis the function is activated as soon as th...

Страница 59: ...00 1200000 ms Determines the dynamic behaviour in the event of a change in the act ive power set value With a voltage change the active power is changed according to a PT 1 characteristic curve with a...

Страница 60: ...nd the con figured gradient the inverter may switch from charging to feed in mode in the event of underfrequency or from feed in to charging mode in the event of overfrequency FEHLENDER LINK The measu...

Страница 61: ...the function in case of underfrequency incidents The active power adjustment is activated if the frequency falls below the configured value and mode 1 or 2 is activ ated In mode 2 the function is deac...

Страница 62: ...ion of the deactivation time P f deactivation gradi ent 0 65534 min If the available power is above the actual output at the time of deactiva tion the power increase back to the maximum power is limit...

Страница 63: ...rters blueplanet gs 50 0 TL3 S have the following characteristics with regard to dynamic grid sup port by way of immunity The ability to remain on the grid is particularly relevant The actual behaviou...

Страница 64: ...ident or to the voltage recovery at the end of the incident take place with the same dynamic The formula for calculating the dynamic reactive current that is fed for the positive or negative phase seq...

Страница 65: ...esult of this the maximum continuous current is not achieved the device supplies additional reactive current according to the formulae 2 and 4 up to the limit of continuous current Zero current under...

Страница 66: ...omponent of the fast feeding of residual current is limited to permit a defined proportion of active power components Minimum support time 1000 15000 ms If due to a voltage jump in accordance with for...

Страница 67: ...the inverters When the inverter is activated or switched on the increase in power is restricted by the set gradient It is possible to con figure whether the soft start up should occur every time the...

Страница 68: ...n low voltage appliances Especially for the last example very fast disconnection of the generating units to cause collapse of the forming island is necessary At the same time any island formation dete...

Страница 69: ...he case if the ROCOF event was due to a short disturbance in the power grid the in verter will resume normal operation In the event of active stage 1 the device switches to zero current mode and re st...

Страница 70: ...rised by the mains supply network operator are permit ted to open and maintain the device Before opening the device Disconnect the AC and DC sides and wait at least 5 minutes NOTE There are components...

Страница 71: ...s on the contact protection 2 Check that the device is voltage free 3 Device version M Run the voltage tester contacts on pole of the DC fuse ter minal device side to the pole of the DC fuse terminal...

Страница 72: ...Never touch the heat sinks after commissioning the device Allow the heat sinks at least 10 minutes to cool down before cleaning NOTE Refer to our service and guarantee conditions on our homepage The...

Страница 73: ...carefully remove the fan downwards T_20 W_7 4 Carefully disconnect the plug connector for the dismounted fan from inside the housing 5 Remove the fan from the base plate Install the replacement fan In...

Страница 74: ...or switch DANGER The DC cables are still live After shutdown wait 5 minutes before opening the device 11 6 Replace DC fuse DANGER Electric shock due to live parts under the protective cover Removing t...

Страница 75: ...tly after be ing switched on Faulty grid separation relay in the device If the grid separation relay is defective the device will recog nise this error during the self test K If the grid separation re...

Страница 76: ...oss of performance failure damage or to a short ening of the device s service life People with very sensitive hearing particularly children are able to hear the high fre quency hum caused by the devic...

Страница 77: ...e device shuts down if the values exceed or fall below the approved levels Fault LED red Status Explanation LED FS fault status Fault signal relay has been tripped To Feed in was ended due to a fault...

Страница 78: ...least 5 minutes Device shut down and no voltage is present AC cable disconnected AC connection DC connection disconnected DC connection 1 Unfasten the cable bolts for Ethernet cables and remove the se...

Страница 79: ...cold to a hot environment Store in accordance with the technical data Environmental data See section 4 3 Page 12 Prior to installation check the inner area for condensation and if necessary allow it...

Страница 80: ...nding transport packaging are made from recyclable raw materials Unit Do not dispose of faulty devices or accessories together with household waste Ensure that the old devices and any accessories are...

Страница 81: ...14 Service and warranty Please contact the suppliers of the energy storage system KACO blueplanet gridsave 50 0TL3 S Page 81 EN...

Страница 82: ...2014 30 EU and the Low Voltage Directive 2014 35 EU The devices conform to the following standards 2014 35 EU Safety of the device Directive relating to electrical equipment designed for use within ce...

Страница 83: ...ical state at the time of printing Subject to technical changes No liability for printing errors Carl Zeiss Strasse 1 74172 Neckarsulm Germany Tel 49 7132 3818 0 Fax 49 7132 3818 703 info kaco newener...

Отзывы: