Country-
spec. Set-
tings
Men
u
level
Display/
Setting
Action in this menu/meaning
4
1
2
3
4
Grid parameter (fur-
ther information)
If the value U< (slow undervoltage shutdown) is set to a value which is
greater than the value of U
con
,
min
(minimum restart voltage) using the LC
display, then the value of U
con
,
min
is automatically set to the value of U>.
If the value U> (slow overvoltage shutdown) is set to a value which is
smaller than the value of U
con
,
max.
(maximum restart voltage) using the
LC display, then the value of U
con
,
max.
is automatically set to the value of
U>.
If the value f< (slow underfrequency shutdown) is set to a value which is
greater than the value of f
con
,
min.
(minimum restart frequency) using the
LC display, then the value of f
con
,
min.
is automatically set to the value of
f<.
If the value f> (slow overfrequency shutdown) is set to a value which is
smaller than the value of f
con
,
max.
(maximum restart frequency) using the
LC display, then the value of f
con
,
max.
is automatically set to the value of
f>.
BE CH-NS
CY DE-NS
DK LU-NS
4
1
2
3
4
Switch-off freq.
NOTE: The device continuously monitors the grid frequency. If the grid
voltage exceeds or drops below the configured values, the device
switches off.
1 Set limit values for underfrequency and overfrequency in 0.1 Hz in-
crements.
2 Set period from occurrence of the fault to shutdown of the device.
4
1
2
3
4
Check surge protection
device
NOTE: Please refer to the application note on our website if you install
the overvoltage protection yourself.
NOTE: Allows the monitoring of the overvoltage protection.
F
Activate overvoltage protection.
NOTE: By activating, an overvoltage protection test is carried out with
an appropriate status messages
4
1
2
3
4
Power limitation.
NOTE: The output power of the device can be set permanently to a
lower value than the maximum output power by the power limitation.
This may be necessary in order to limit the maximum power rating of
the system at the grid connection point, upon the grid operator's re-
quest.
NOTE: The value can be protected from the very first power limitation
entry. After setting a limitation, the value can only be changed by en-
tering a device-specific password.
NOTE: Only the external power limitation can be adjusted on the
device. The internal power limitation can only be set via the web inter-
face.
Configuration via web user interface [See section 9.3.2
4
1
2
3
4
Power limitation. ex-
ternal
NOTE: External power limitation is possible with the extension module
(KACO accessories).
1 Specify the activation status (
on / off
).
2 Select the activation threshold (Active Low / Active High) from di-
gital input 1, 2, 3 or 4 (only if activation status = on).
3 Specify the power limitation stages (only if activation status = on) a.)
Specify stage 0-3 b.) Specify stage 4-7 c.) Specify stage 8-11 d.) Spe-
cify stage 12-15
4 Confirm the entry with the
Enter
button.
KACO blueplanet gridsave 50.0TL3-S
Page 37
EN