Country-
spec. Set-
tings
Level Display/
Setting
Action in this menu/meaning
4
1
2
3
4
Evaluated voltage
Maximum phase
voltage | Positive
phase sequence
voltage
F
Select the voltage to be rated.
Specifies which voltage is evaluated in a three-phase system.
4
1
2
3
4
Hysteresis mode
Off | On
NOTE: Hysteresis mode affects the shutdown response of P(U).
F
Activate the mode.
4
1
2
3
4
Deactivation gradient
0 – 65534 [% / min]
F
Set the gradients for the power limitation.
Not for IL,
IT
4
1
2
3
4
Deactivation time
0 – 60000000 [ms]
F
Specify the time for voltage reduction.
4
1
2
3
4
Output gradient limita-
tion increase & Output
gradient limitation de-
crease
1 - 65534 [% / min]
F
Specify the increasing and decreasing output gradient.
4
1
2
3
4
Active curve
1 - 5
F
Select active curve.
NOTE: Up to 5 characteristic curves can be configured independently
and one of them can be activated for regulation each time.
4
1
2
3
4
Power rampup active
NOTE: Power ramp-up is used to ramp up the power gradually
Power rampup gradi-
ent
1 – 600 [% / min]
F
Set increase.
Rampup on every con-
nect
Status
Rampup on first con-
nect
Status
Rampup after grid fail-
ure
Status
Password Protection
Status
1 Activate option.
2 Activate optional password protection.
3 Confirm action field
4
1
2
3
4
Average value over ten
minutes
Overvoltage aver-
aging
F
Set the voltage via averaging.
Counter / inverter
voltage drop
F
Set the voltage.
KACO blueplanet gridsave 50.0TL3-S
Page 47
EN