10.2.3.1 Parameters for P(f)
Country-
spec. Set-
tings
Men
u
level
Display/
Setting
Action in this menu/meaning
P(f) operation mode
Off | Mode 1 |
Mode 2
Activate or deactivate function.
Mode 1: With hysteresis activated. See figure 3.
Mode 2: Without hysteresis activated. --- FEHLENDER LINK ---
Power reference mode
with overfrequency
Actual power |
Nominal power
Power reference mode
with underfrequency
Actual power |
Nominal power
Power reference with overfrequency:
Power reference for power adjustment as in equation 6 and equation 7
for overfrequency incidents.
Power reference with underfrequency:
Power reference for power adjustment as in equation 6 and equation 7
for overfrequency incidents.
Activation threshold
with overfrequency
50.2 – 70 (Hz)
Activation threshold
with underfrequency
40 – 45 (Hz)
Activation threshold (f1) overfrequency:
Determines the frequency threshold for activating the function in case
of overfrequency incidents. The active power adjustment is activated if
the frequency rises above the configured value and mode 1 or 2 is activ-
ated.
In mode 2, the function is deactivated if the frequency falls below the
configured value.
Activation threshold (f1) underfrequency:
Determines the frequency threshold for activating the function in case
of underfrequency incidents. The active power adjustment is activated if
the frequency falls below the configured value and mode 1 or 2 is activ-
ated.
In mode 2, the function is deactivated if the frequency rises above the
configured value.
Gradient with overfre-
quency – feed-in
0 – 200 (%/Hz) 40
(%/Hz)
Gradient with under-
frequency – feed-in
0 – 200 (%/Hz) 40
(%/Hz)
Gradient with overfrequency (feed-in):
Determines the active power adjustment in accordance with equation 2
and equation 3, subject to the frequency.
Gradient for overfrequency incidents if the incident begins in feed-in
mode.
Gradient with underfrequency (feed-in):
Determines the active power adjustment in accordance with equation 2
and equation 3, subject to the frequency.
Gradient for underfrequency incidents if the incident begins in feed-in
mode.
Gradient with overfre-
quency – charging
0 – 200 (%/Hz) ;
40 (%/Hz)
Gradient with under-
frequency – charging
0 – 200 (%/Hz) ;
40 (%/Hz)
Gradient with overfrequency (charging):
Determines the active power adjustment in accordance with equation 2
and equation 3, subject to the frequency.
Gradient for overfrequency incidents if the incident begins in charging
mode.
Gradient with underfrequency (charging):
Determines the active power adjustment in accordance with equation 2
and equation 3, subject to the frequency.
Gradient for underfrequency incidents if the incident begins in charging
mode.
KACO blueplanet gridsave 50.0TL3-S
Page 61
EN