NETCOM6P Installation Guide
15
Steps to Program and Install a NETCOM6P/ACU Control Board …cont’d
21.
Wait while the NETCOM Program tool utility programs the NETCOM device.
If the NETCOM does not program on the 1st attempt, keep the NETCOM Program
Settings screen open and press the F4 key. Click inside the box to the left of
Program Server Address Settings Only so it has a check mark. Ensure the
settings have been retained, including the IP Address, otherwise re-enter them.
Click on the Program NETCOM button. If successful, program the NETCOM one
more time. For additional programming tips, press the F1 key with the Keyscan
NETCOM Program Settings screen open.
22.
When prompted, disconnect the serial cable from the RS-232 (COM4) terminal on the
control board.
23.
Connect the NETCOM6P to the network.
24.
Do one of the following steps:
Remove the jumper from J16 – pin G. However, leave the jumper ON pin F. This
enables M1 for communication with the NETCOM6P.
Set S2 switch 8 to OFF, but leave S2 switch 7 ON so M1 is enabled for
communication with the NETCOM6P
25.
Momentarily place a jumper ON J6 Reset or press the S1 switch on the control board.
26.
At the PC/laptop, click on the OK button in the Disconnect the serial cable… screen.
27.
If the PC/laptop has a network connection, verify network communication with the
NETCOM6P. Select the Start PING button on the Keyscan NETCOM Utility screen.
If the PC/laptop does not have a network connection, close the NETCOM Program
Tool utility, complete any remaining connections for permanent operation, re-
locate to a PC connected to the network and PING the NETCOM2’s IP address
using the Command Prompt. The Average Round Trip Times should be less than
100 milliseconds and the Packets Sent should equal the Packets Received with
0% loss. Continue at step 29.
28.
Wait for the PING Status result message:
IP Success indicates the NETCOM6P has network communication
IP Timed Out indicates the NETCOM6P does not have network communication—
verify settings and connections
29.
Click on the x in the upper right corner of the Keyscan NETCOM Utility screen to close
the application.
30.
Disconnect the power from the ACU control board.
31.
Re-mount the ACU protective cover.
32.
Re-apply power after the ACU protective cover has been re-mounted.
33.
Do one of the following procedures depending on the version of PC109x control board.
J16 Jumpers - After applying power, place a jumper ON J16—pin H, then
momentarily place a jumper on J1—Clear Memory to reconfigure the on-board
memory. Allow approximately 2 minute and do not make any changes while the
control board re-configures. Remove the jumper from J16—pin H.
S1 & S3 Switches - After applying power, press S1, wait 5 seconds, then within
10 seconds press S3 to reconfigure the on-board memory. Allow approximately 2
minute and do not make any changes while the control board re-configures.
34.
Close and secure the ACU enclosure door.
35.
Depending on the type of installation do one of the following steps:
If this is a new installation, install the Keyscan software, set up the site, and
perform a full panel upload.
If this is an existing installation, log on to a Client software module, edit the site
setup screens, and perform a full panel upload.