Installation and Start up cont.
INSTALLATION OF OPTIONAL LEVEL ALARMS OUTPUTS
The alarm output board allows for 24-120Vac relays that arecurrently programmed for HI
and LO level alarm outputs on Channels 1-12. See DATA SHEET #DS-112890AO- K1600
ALARM OUTPUTS for installation of external wiring.
INSTALLATION OF OPTIONAL RS232 COMMUNICATION
An RS232 communication port is provided for downloading inventory information to a host
computer on demand. For Cable connections, Software protocal and transmission information
refer to Data Sheet #DS-010191SC REV 1 - K1600 SERIAL COMMUNICATION BOARD and Data
Sheet #DS-010291TMAD - TRANSMITTER INPUT & COMMUNICATION DATA.
INSTALLATION OF OPTIONAL ALARM HORN
Mount horn in desired location per the mounting instructions provided with the horn. connect
horn wiring according to Data Sheet #DS-100591OH and DS-022792AH
OPERATION AND START UP
Before introducing power to the inventory system, check to see that all connections are tight
and made to the correct terminal. Turn the power switch on the power supply board to the "ON"
position and the system should power up and momentarily display the K Systems Initialization
Screen and then display the Multi-tank Inventory screen. If this does not occur turn off the
System, check the incoming power connections and restart again.
The K1600 is now running and will show inventory values based on the tank and information
provided prior to shipment.
If an alarm condition is present the GENERAL ALARM
STATUS LINE will appear and the alarm condition will have to be acknowledged
by pressing the <ACK> pushbutton. Several alarms may have to be
acknowledged.
The inventory values shown after all alarms have been akcnowledged should
reflect the "RESERVE" values assuming the tanks are empty. The "RESERVE" values represent
the amount of product in the tank below the sensor that obviously cannot be sensed by the tank
transmitters and will be the lowest value displayed by the system. As Product is being
introduced into the tank the display will not register until the "RESERVE" value is exceeded.