Programming cont.
When the proper access code is entered the Single tank Alarm level screen will reappear with a
flashing cursor over the first number that can be changed.
If the cursor is over the level value to be changed then enter the proper value through the keypad and press
<ENTER>
. A valid entry is between 0 and 99,999 gallons. When
<ENTER>
is pressed the cursor moves
to the next programmable data field. If the cursor is not over the desired value press
<ENTER>
or the
<UP-DOWN SCROLL>
buttons to move the cursor. The
<DELETE>
button will erase an entry.
To change the low value to 250 gallons press
<2> <5> <0> <ENTER>.
If all the values shown are correct then press the
<RUN/PAGE>
button to return to the inventory display.
As previously indicated all level setpoints are programmed in gallons regardless of the normal inventory
display units. In addition, when the alarm values are entered, if the current volume in the tank meets the
alarm condition the
GENERAL ALARM STATUS LINE
will appear and the alarm will have to be silenced
and acknowledged. In doing so, the programming function is automatically turned off and the
<PROG>
button will have to be pressed and access codes re-entered.
TANK 5 ALARMS CH:5
LO LEVEL: 500 GALS
MD LEVEL: 1500 GALS
HI LEVEL: 4000 GALS
TANK 5 ALARMS CH:5
LO LEVEL: 250 GALS
MD LEVEL: 1500 GALS
HI LEVEL: 4000 GALS