•
Ensure that the polarity of the DC input wiring is correct. Under certain conditions,
connections with reversed polarity might trip the primary circuit breaker or damage
the equipment.
•
For personal safety, connect the green and yellow wire to safety (earth) ground at both
the services gateway and the supply side of the DC wiring.
•
The marked input voltage of –48 VDC for a DC-powered services gateway is the nominal
voltage associated with the battery circuit, and any higher voltages are only to be
associated with float voltages for the charging function.
•
Because the services gateway is a positive ground system, you must connect the
positive lead to the terminal labeled
RETURN
, the negative lead to the terminal labeled
–48V
, and the earth ground to the chassis grounding points.
DC Power Disconnection Warning
WARNING:
Before performing any of the following procedures, ensure that
power is removed from the DC circuit. To ensure that all power is off, locate
the circuit breaker on the panel board that services the DC circuit, switch the
circuit breaker to the
OFF
position, and tape the switch handle of the circuit
breaker in the
OFF
position.
Waarschuwing
Voordat u een van de onderstaande procedures uitvoert,
dient u te controleren of de stroom naar het gelijkstroom circuit uitgeschakeld
is. Om u ervan te verzekeren dat alle stroom UIT is geschakeld, kiest u op het
schakelbord de stroomverbreker die het gelijkstroom circuit bedient, draait
de stroomverbreker naar de UIT positie en plakt de schakelaarhendel van de
stroomverbreker met plakband in de UIT positie vast.
Varoitus
Varmista, että tasavirtapiirissä ei ole virtaa ennen seuraavien
toimenpiteiden suorittamista. Varmistaaksesi, että virta on KATKAISTU
täysin, paikanna tasavirrasta huolehtivassa kojetaulussa sijaitseva suojakytkin,
käännä suojakytkin KATKAISTU-asentoon ja teippaa suojakytkimen varsi
niin, että se pysyy KATKAISTU-asennossa.
Attention
Avant de pratiquer l'une quelconque des procédures ci-dessous,
vérifier que le circuit en courant continu n'est plus sous tension. Pour en être
sûr, localiser le disjoncteur situé sur le panneau de service du circuit en courant
continu, placer le disjoncteur en position fermée (OFF) et, à l'aide d'un ruban
adhésif, bloquer la poignée du disjoncteur en position OFF.
Warnung
Vor Ausführung der folgenden Vorgänge ist sicherzustellen, daß
die Gleichstromschaltung keinen Strom erhält. Um sicherzustellen, daß
sämtlicher Strom abgestellt ist, machen Sie auf der Schalttafel den
Unterbrecher für die Gleichstromschaltung ausfindig, stellen Sie den
Unterbrecher auf AUS, und kleben Sie den Schaltergriff des Unterbrechers
mit Klebeband in der AUS-Stellung fest.
Copyright © 2015, Juniper Networks, Inc.
162
SRX240 Services Gateway Hardware Guide
Содержание SRX240 Series
Страница 1: ...SRX240 Services Gateway Hardware Guide Modified 2015 06 08 Copyright 2015 Juniper Networks Inc ...
Страница 8: ...Copyright 2015 Juniper Networks Inc viii SRX240 Services Gateway Hardware Guide ...
Страница 18: ...Copyright 2015 Juniper Networks Inc xviii SRX240 Services Gateway Hardware Guide ...
Страница 20: ...Copyright 2015 Juniper Networks Inc 2 SRX240 Services Gateway Hardware Guide ...
Страница 26: ...Copyright 2015 Juniper Networks Inc 8 SRX240 Services Gateway Hardware Guide ...
Страница 30: ...Copyright 2015 Juniper Networks Inc 12 SRX240 Services Gateway Hardware Guide ...
Страница 46: ...Copyright 2015 Juniper Networks Inc 28 SRX240 Services Gateway Hardware Guide ...
Страница 58: ...Copyright 2015 Juniper Networks Inc 40 SRX240 Services Gateway Hardware Guide ...
Страница 62: ...Copyright 2015 Juniper Networks Inc 44 SRX240 Services Gateway Hardware Guide ...
Страница 64: ...Copyright 2015 Juniper Networks Inc 46 SRX240 Services Gateway Hardware Guide ...
Страница 72: ...To install the device in a rack Copyright 2015 Juniper Networks Inc 54 SRX240 Services Gateway Hardware Guide ...
Страница 76: ...Copyright 2015 Juniper Networks Inc 58 SRX240 Services Gateway Hardware Guide ...
Страница 80: ...Copyright 2015 Juniper Networks Inc 62 SRX240 Services Gateway Hardware Guide ...
Страница 86: ...Copyright 2015 Juniper Networks Inc 68 SRX240 Services Gateway Hardware Guide ...
Страница 96: ...Copyright 2015 Juniper Networks Inc 78 SRX240 Services Gateway Hardware Guide ...
Страница 120: ...Copyright 2015 Juniper Networks Inc 102 SRX240 Services Gateway Hardware Guide ...
Страница 122: ...Copyright 2015 Juniper Networks Inc 104 SRX240 Services Gateway Hardware Guide ...
Страница 138: ...Copyright 2015 Juniper Networks Inc 120 SRX240 Services Gateway Hardware Guide ...
Страница 142: ...Copyright 2015 Juniper Networks Inc 124 SRX240 Services Gateway Hardware Guide ...
Страница 148: ...Copyright 2015 Juniper Networks Inc 130 SRX240 Services Gateway Hardware Guide ...
Страница 150: ...Copyright 2015 Juniper Networks Inc 132 SRX240 Services Gateway Hardware Guide ...
Страница 158: ...Copyright 2015 Juniper Networks Inc 140 SRX240 Services Gateway Hardware Guide ...
Страница 186: ...Copyright 2015 Juniper Networks Inc 168 SRX240 Services Gateway Hardware Guide ...
Страница 192: ...Copyright 2015 Juniper Networks Inc 174 SRX240 Services Gateway Hardware Guide ...
Страница 193: ...PART 7 Index Index on page 177 175 Copyright 2015 Juniper Networks Inc ...
Страница 194: ...Copyright 2015 Juniper Networks Inc 176 SRX240 Services Gateway Hardware Guide ...
Страница 198: ...Copyright 2015 Juniper Networks Inc 180 SRX240 Services Gateway Hardware Guide ...