13.
Reinstall the metal PDM wiring cover, and using a number 2 Phillips (+) screwdriver,
tighten the four captive screws on the metal AC wiring compartment.
14.
Use the provided plastic cable tie to fasten the AC power cord to the PDM.
15.
Verify that the AC power cord does not touch or block access to router components,
and that it does not drape where people could trip on it.
16.
Repeat the procedure for the other three-phase wye AC PDMs.
17.
Connect the three-phase wye AC power cord mating connector to the AC power cord
connector (see
).
shows the approved
three-phase wye AC power cord mating connector specifications.
Figure 37: Three-Phase Wye AC Power Cord Mating Connector
g000038
Table 7: Three-Phase Wye AC Power Cord Mating Cable Connector
Specifications
Description
Manufacturer Part Number
Cable
32-amp, 400 volt IP44 3 pole,
5 wire with brass contacts (red)
PCE 225-6
Three-phase wye
NOTE:
The three-phase wye AC power cord mating connector is not
supplied by Juniper Networks.
WARNING:
Do not touch the power connectors on the PDM. They can contain
dangerous voltages.
Copyright © 2017, Juniper Networks, Inc.
52
MX2008 3D Universal Edge Router Quick Start