eNet radio DALI gateway 1-gang mini

Parameters

Setting options, Basic setting

Explanations

will remain off. 
Note: The set time apply to
operation using radio transmit-
ters. The device is switched
immediately when the Prog
button is pressed.

Switch-off delay

0 s … 24 h
Basic setting: 0 s

The load switches off after a
delay. Repeated switch-off
commands restart the delay
time. If the load has not yet
been switched off due to the
delay when a switch-on com-
mand comes, then the load
will remain on.
Note: The set time apply to
operation using radio transmit-
ters. The device is switched
immediately when the Prog
button is pressed.

Dim up ramp

0 s … 24 h
Basic setting: 0 s

Time between switch-on and
reaching switch-on brightness.
The light is switched on at
minimum brightness and then
dimmed to the switch-on
brightness. 
Only applies to switch-on with
transmitters (short operation).
If scenes are recalled or
switching uses logic modules,
the switch-on brightness is ap-
proached using so-called soft
dimming (not configurable).

Dim down ramp

0 s … 24 h
Basic setting: 0 s

Time until reaching minimum
brightness. The light is
dimmed to minimum bright-
ness and then switched off.
Only applies to switch-off with
transmitters (short operation).
If scenes are recalled or
switching uses logic modules,
the system switches off dir-
ectly.

Run-on time

0 s … 24 h
Basic setting: 0 s

As soon as a run-on time has
been entered, the actuator will
no longer remain on perman-
ently, but only for the length of
the run-on time. The run-on
time is restarted if actuation is
repeated. This parameter is
directly connected to the
"Manual switch-off of run-on
time" parameter. 
Note: The set time apply to
operation using radio transmit-

8 / 13

82580933

22.08.2019

J0082580933

Содержание FMSTD8UP

Страница 1: ...an integral part of the product and must remain with the end customer 2 Device components Figure 1 Front view 1 Operating mode switch 2 Button Prog 3 Status LED 4 Measuring points for voltage measurem...

Страница 2: ...ission AES CCM from eNet Server software version 2 0 Update of the device software Repeater function Reading of error memory Behaviour after mains voltage failure and return The response after mains v...

Страница 3: ...rs The control cable and load cable can be run in a shared cable e g NYM J 5 1 5 Ensure that the control cable with regards type cross section and routing complies with the VDE specifications for 250...

Страница 4: ...switched off Press button Prog 2 for longer than 4 seconds The status LED 3 flashes after 4 seconds The control unit is in programming mode for approx 1 minute Switch radio transmitter to programming...

Страница 5: ...ng the minimum brightness The minimum brightness can be set within a range of approx 1 67 if e g the light flickers at low brightness or to compensate for differences in brightness Switch on light Tur...

Страница 6: ...eNet server Device and channels Parameters Setting options Basic setting Explanations Function Light unused Basic setting Light Light The channel is integrated for the Lighting central function in th...

Страница 7: ...ness Note If the value is above the set maximum brightness or below the minimum bright ness then the system will switch to the appropriate limit value Minimum brightness 1 67 Basic setting 5 Specifies...

Страница 8: ...ness and then dimmed to the switch on brightness Only applies to switch on with transmitters short operation If scenes are recalled or switching uses logic modules the switch on brightness is ap proac...

Страница 9: ...tions Basic setting Explanations Operating mode Normal operation Continuous on Continuous off Basic setting Normal Opera tion see Device and channels Manual commissioning On Off Basic setting On Block...

Страница 10: ...tch off command restarts the time for the switch off warning Note The set time apply to operation using radio transmit ters The device is switched immediately when the Prog button is pressed Priority...

Страница 11: ...0 100 Basic setting 100 Defines the behaviour of the output on activating the sun protection Deactivate sun protection brightness value 0 100 Basic setting 0 Defines the behaviour of the output on de...

Страница 12: ...ness when the hotel function is ac tivated Information window In the Information window the load can be controlled and the information about the device can be displays Channel control channel informat...

Страница 13: ...ccessories Mounting adapter for mini housing Art no FM EBG eNet server for rail mounting Art no ENET SERVER 10 Conformity Hereby Albrecht Jung GmbH Co KG declares that the radio system type Art no FMS...

Отзывы: