Jung FMSTD8UP Скачать руководство пользователя страница 5

eNet radio DALI gateway 1-gang mini

The status LED (3) flashes quickly for 5 seconds. The control unit is disconnected from
the radio transmitter. The control unit and radio transmitter exit the programming mode
automatically.

If there several connections or scene buttons for a radio transmitter, all connections must
be disconnected individually.

All On and All Off buttons of a radio transmitter are disconnected automatically as soon as
the last connection to the radio transmitter is disconnected. Manual disconnection is not
possible.

Resetting control unit to the default setting

All connections to radio transmitters are disconnected and parameters are reset to default set-
ting.

The connections in the radio transmitters are preserved and must be deleted separately.

Load is switched off.

Press the Prog button for at least 20 seconds.
The status LED flashes after 4 seconds. After 20 seconds the status LED flashes faster.

Release Prog button and press briefly once again within 10 seconds.
The status LED flashes more slowly for approx. 5 seconds.

Reset control unit to default setting.

Setting the minimum brightness

The minimum brightness can be set within a range of approx. 1...67 %, if, e.g. the light flickers
at low brightness or to compensate for differences in brightness.

Switch on light.

Turn operating mode switch (1) to the min. position.
The light switches to maximum brightness for approx. 2 seconds.

The light switches off and after approx. 2 seconds switches to the brightness that was last
set.

Adjust brightness with the radio transmitter.

Turn operating mode switch to the original position again.
When leaving the position min., the minimum brightness is saved. As confirmation, the
light switches to maximum brightness and switches to the set minimum brightness after
approx. 2 seconds.

Depending on the DALI ballast used, the signalling may vary from what is described here.

Save switch-on brightness

Switch on light.

Adjust brightness with the radio transmitter.

Press button Prog (2) for longer than 4 seconds.
The light switches off briefly and then switches on again to the new switch-on brightness.

Switch-on brightness is saved.

Alternatively, the switch-on brightness can be saved with a radio transmitter, e.g. wall
transmitter.

6

Technical data

Rated voltage

AC 230 V~

Mains frequency

50 / 60 Hz

Power consumption

max. 2 W

Ambient temperature

-25 ... +70 °C

5 / 13

82580933

22.08.2019

J0082580933

Содержание FMSTD8UP

Страница 1: ...an integral part of the product and must remain with the end customer 2 Device components Figure 1 Front view 1 Operating mode switch 2 Button Prog 3 Status LED 4 Measuring points for voltage measurem...

Страница 2: ...ission AES CCM from eNet Server software version 2 0 Update of the device software Repeater function Reading of error memory Behaviour after mains voltage failure and return The response after mains v...

Страница 3: ...rs The control cable and load cable can be run in a shared cable e g NYM J 5 1 5 Ensure that the control cable with regards type cross section and routing complies with the VDE specifications for 250...

Страница 4: ...switched off Press button Prog 2 for longer than 4 seconds The status LED 3 flashes after 4 seconds The control unit is in programming mode for approx 1 minute Switch radio transmitter to programming...

Страница 5: ...ng the minimum brightness The minimum brightness can be set within a range of approx 1 67 if e g the light flickers at low brightness or to compensate for differences in brightness Switch on light Tur...

Страница 6: ...eNet server Device and channels Parameters Setting options Basic setting Explanations Function Light unused Basic setting Light Light The channel is integrated for the Lighting central function in th...

Страница 7: ...ness Note If the value is above the set maximum brightness or below the minimum bright ness then the system will switch to the appropriate limit value Minimum brightness 1 67 Basic setting 5 Specifies...

Страница 8: ...ness and then dimmed to the switch on brightness Only applies to switch on with transmitters short operation If scenes are recalled or switching uses logic modules the switch on brightness is ap proac...

Страница 9: ...tions Basic setting Explanations Operating mode Normal operation Continuous on Continuous off Basic setting Normal Opera tion see Device and channels Manual commissioning On Off Basic setting On Block...

Страница 10: ...tch off command restarts the time for the switch off warning Note The set time apply to operation using radio transmit ters The device is switched immediately when the Prog button is pressed Priority...

Страница 11: ...0 100 Basic setting 100 Defines the behaviour of the output on activating the sun protection Deactivate sun protection brightness value 0 100 Basic setting 0 Defines the behaviour of the output on de...

Страница 12: ...ness when the hotel function is ac tivated Information window In the Information window the load can be controlled and the information about the device can be displays Channel control channel informat...

Страница 13: ...ccessories Mounting adapter for mini housing Art no FM EBG eNet server for rail mounting Art no ENET SERVER 10 Conformity Hereby Albrecht Jung GmbH Co KG declares that the radio system type Art no FMS...

Отзывы: