eNet radio DALI gateway 1-gang mini
Parameters
Setting options, Basic setting
Explanations
Switch on brightness under-
shoot
On, Off
Basic setting: Off
Allows automatic switch-on
according to the brightness. If
the parameter is On, then the
light controller switches on
automatically when the bright-
ness setpoint is greatly under-
shot. We recommend only us-
ing the parameter in connec-
tion with the parameter
"Switch-off on brightness over-
shoot".
Note: This parameter is not
yet active, as a light controller
has not yet been implemen-
ted.
Hotel function
On, Off
Basic setting: Off
If the hotel function is activ-
ated, the system will dim to 20
% brightness when a switch-
off command is made. Switch-
off is only possible with a
forced position command.
Note: If the minimum bright-
ness is set to greater than 20
%, then the system dims to
the set minimum brightness
when the hotel function is ac-
tivated.
Information window
In the Information window, the load can be controlled and the information about the device can
be displays.
Channel control/channel information
Display value
Explanations
Current dimming value
The load can be dimmed using the slider or a
brightness value entry.
Load state
The load can be switched on or off.
Restraint
Display of forced position status.
Operating hours
Display of the operating hours since the last
restart in the Settings window Einstellungen.
8
Troubleshooting
DALI ballasts switch to System-Failure-Level. No operation is possible.
Cause 1: short-circuit protection of the control unit has triggered, DALI voltage is switched off.
Status LED (3) flashes 3 times at intervals of 1 second.
Disconnect control unit from mains, also switch off circuit breaker.
Eliminate short-circuit.
Switch circuit breakers and control unit on again.
Short-circuit protection is not based on a conventional fuse, no metallic separation of the
DALI current.
12 / 13
82580933
22.08.2019