eNet radio DALI gateway 1-gang mini
5
Information for electrically skilled persons
5.1 Fitting and electrical connection
DANGER!
Electrical shock when live parts are touched.
Electrical shocks can be fatal.
Before carrying out work on the device or load, disengage all the corresponding cir-
cuit breakers. Cover up live parts in the working environment.
Connecting and mounting the control unit.
To ensure good transmission quality, keep a sufficient distance from any possible sources of in-
terference, e.g. metallic surfaces, microwave ovens, hi-fi and TV systems, ballasts or trans-
formers.
Figure 2: Connection example
The connected DALI subscribers may be operated on different phase conductors.
The control cable and load cable can be run in a shared cable, e.g. NYM J 5×1.5.
Ensure that the control cable with regards type, cross-section and routing complies with
the VDE specifications for 250 V cables, DALI interface has basic insulation.
■
Connect control unit (5) and DALI ballasts (6) as shown in the connection example
(Figure 2). At the same time, note the information given by the manufacturers of the bal-
lasts.
In the case of more than 12 DALI subscribers, up to five additional control units can be
connected. When doing so, ensure correct polarity.
■
If multiple circuit breakers supply dangerous voltages to the device or load, couple the
miniature circuit breakers or label them with a warning, to ensure disconnection is guaran-
teed.
■
Insert the control unit into the appliance box in such a way that the Prog button (2) and
status-LED (3) are visible.
3 / 13
82580933
22.08.2019
J0082580933