9 Calibrating a sensor with a standard signal
9.2
Linear operating mode
9.2.1
1-point calibration
The transmitter is in "Measuring mode".
✱
Now bring the system to a defined state (e.g. when measuring liquid level,
empty the container).
✱
Start the calibration, see "Ways to start the calibration", page 54.
✱
Select the zero point calibration with the
key.
✱
Wait until the display value has stabilized; then press
to continue.
Set the displayed value to the required value (usually 0%) with the
and
keys; then press
to continue.
The zero point determined by the instrument is displayed.
Use the
key to accept the value or
the
key to reject it.
This example is based on a liquid level measurement (as a %).
The input signal is provided by a pressure transmitter.
PGM
PGM
PGM
PGM
EXIT