33
7 Startup
7.8
Setting scaling
User-specific measuring range
The user measuring range (2) is defined by:
•
Measuring range start (4)
•
Measuring range end (5)
•
Measuring span (MSP)
Example:
Actual
The device has a nominal measuring range (1) from 0 to 4 bar.
Target
The user would like to measure the pressure in the range from 1 to 2 bar (25 % of nominal
measuring range).
Measuring range start (4) is 1 bar.
Measuring range end (5) is 2 bar.
Measuring span (MSP) is 1 bar.
0
4
b
ar
2
1
1
2
3
5
4