7 Technical data
24
7.5
Environmental influences
Hysteresis in %
of the control/limit value range
(only for type 2 and 20)
Reted value
Possible process value
Designation
3
3 to 4
S1
6
6 to 8
S2
1.5
1 to 2
S3
Switching point accuracy
Of the control/limit value at T
U
22 °C
TW
In the upper third of the scale ±1.5 %, at the beginning of the scale ±6 %,
STB, STW (STB)
in the upper third of the scale +0/-5 %, at the beginning of the scale +0/-10 %
Setpoint value adjustment
Switching point adjustable with screwdriver after removing housing cover.
Ambient temperature influence
Referring to the control/limit value range
If the ambient temperature at the switching head and/or the capillary deviates
from the calibration ambient temperature 22 °C, a switching point shift occurs.
Higher ambient temperatures
= lower switching point
Lower ambient temperatures
= higher switching point
For devices with scale limit value < 200 °C
≥ 200 °C
ATH.-SE-2
ATH.-SE-20
ATH.-SE-2
ATH.-SE-20
ATH.-SE-70
ATH.-SE-70
On switching head
0.08 %/K
0.17 %/K
0.06 %/K
0.13 %/K
On capillary per m
0.047 %/K
0.054 %/K
0.09 %/K
0.11 %/K
Admissible ambient temperature
Capillary, switching head
Max. 80 °C
Min. -40 °C at the end of the scale < 200 °C
Min. -20 °C at the end of the scale ≥ 200 °C ≤ 300 °C
Admissible storage temperature
-50 to +50 °C
Permissible overtemperature safe-
ty
Max. scale end value +15 % on the probe during use
Time constant t
0,632
In water
≤ 45 s
In oil
≤ 60 s
In air, superheated steam
≤ 120 s
Protection type
IP54, according to EN 60529