13
4 Mounting
4.3
Fixing the device
Operating position: Any, for open-air mounting on request
4.3.1
Code "s" (rigid shaft)
The housing journal is secured in the enlarged open end of the thermowell by two fixing screws.
4.3.2
Code "f" (with capillary)
Fixing is by G 1/2 screw connection on the housing spigot.
4.4
Capillary, temperature probe and thermowell
4.4.1
General information
CAUTION!
Failure of the device
Cutting through or kinking the capillary will lead to permanent failure of the device!
Minimum permissible bending radius of the capillary is 5 mm.
The temperature probe must be fitted in a JUMO thermowell, otherwise the approval of the device ex-
pires.
NOTE!
The temperatur probe must be completely submerged in the medium.
In order to ensure the general accuracy of response, the devices must only be used with the thermowells
supplied from the factory (diameter D = 8 or 10 mm).
Only probes with a diameter D = 8 mm may be fitted in thermowells with a diameter D = 10 mm.
When the operating medium is air, connection type „10“ (without thermowell) must be selected.
4.4.2
Approved process connections
Temperature probe
Process connection 10: Plain cylindrical probe (only with ATHf-SE)
Thermowells
Process connection 20: Screw-in thermowell,
process connection 30: Screw-in thermowell with intermediate piece
NOTE!
For detailed information, refer to data sheet 606710.