17
5 Installation
5.2
Connection diagram
5.2.1
Opening the housing
1. Open the housing,
chapter 4.2 "Opening the housing", Page 12.
2. Pass the connection cable (cable diameter 10 to 16.5 mm) through the screw connection (C);
fitting type „X“ (no special tools), screw connection up to 2.5 mm
2
conductor cross-section.
3. Establish the connection to the terminals (A) in accordance with the appropriate connectin diagram.
4. Connect the protective conductor to terminal PE (B).
NOTE!
Tightening torque of the clamping screws/protective earth conductor clamp (PE) = 0.45 to 0.68 Nm
Wiring diagrams
TW/STW (STB)
STB as N/C contact with signal contact
STB with N/C contact