2 Device versions
10
2.5
JUMO flowTRANS MAG S/H - remote mount design
The transmitter is mounted at a separate location from the sensor. The electrical connection between
the transmitter and sensor may only be established using the signal cable included in the scope of de-
livery.
see chapter 2.5.3 "Signal cable length and preamplifier", page 12.
2.5.1
ATEX/IECEx Zone 1
The electrical connection between the transmitter and sensor may only be established using the signal
cable included in the scope of delivery.
see chapter 2.5.3 "Signal cable length and preamplifier",
page 12.
DANGER - Risk of explosion caused by incorrect transmitter installation!
The transmitters 406018/2-0 and 406019/2-0 are not Ex-approved.
The transmitters 406018/2-0 and 406019/2-0 must not be installed or operated in potentially explosive
areas.
JUMO flowTRANS MAG S01/S02
JUMO flowTRANS MAG 01/02
406012/2-1 (Ex-protection zone 1)
406018/2-1 (Ex-protection zone 1)
406013/2-1 (Ex-protection zone 1)
406019/2-1 (Ex-protection zone 1)
Sensor:
aluminum housing
Transmitter:
dual-compartment housing
ATEX certificate:
FM15ATEX0025X
ATEX certificate:
FM15ATEX0025X
DN 3 to 300: II 2 G Ex d e ia ma IIC T6 ... T2 Gb II 2 (2) G Ex d e [ia Gb] IIC T6
> DN 300:
II 2 G Ex d e ia IIC T6…T2 Gb
II 2 D Ex ia tb IIIC T70° C ... T
Medium
II 2 (2) D Ex tb [ia Db] IIIC T70° C Db
IECEx certificate:
FME 15.0006X
IECEx certificate:
FME 15.0006X
DN 3 to 300: Ex e ia ma IIC T6 ... T2 Gb
Ex d e [ia Gb] IIC T6 Gb
> DN 300:
Ex e ia IIC T6 ... T2 Gb
Ex tb IIIC T70° C ... T
Medium
Ex tb [ia Db] IIIC T70° C Db
NOTE
The JUMO flowTRANS MAG H model series with a remote mount design is not available for ATEX/
IECEx zone 1.