63
13 Eliminating faults and malfunctions
Example 2
The measuring transmitter is to show 500 mS:
To achieve a display of 500 mS/cm, the resistance loop (with 3 turns) must
have a resistance of 112.5 Ohm.
Precalculated
values
Test
sequence
✱
Calculate the test resistance.
✱
Wire up the device, see Chapter 7 "Installation", Page 25.
✱
Select the corresponding measurement range, see Chapter 10.6.1
"CONDUCTIVITY IN (Conductivity input)", Page 37 -> RANGE 1 — 4
✱
Set TC to 0%/°C, see Chapter 10.6.1 "CONDUCTIVITY IN (Conductivity
input)", Page 37 -> TEMPCO
✱
Fit the resistance loop as shown in the diagram.
R =
3
2
·6.25 1/cm
= 112.5
Ω
500·10
-3
S/cm
Required display
Number of
turns
Required resistance
0 µS/cm
0
no resistance
625 µS/cm
1
10000
Ω
1000 µS/cm
1
6250
Ω
2000 µS/cm
1
3125
Ω
5000 µS/cm
1
1250
Ω
10 mS/cm
1
625
Ω
20 mS/cm
1
312.5
Ω
50 mS/cm
3
1125
Ω
100 mS/cm
3
562.5
Ω
200 mS/cm
3
281.3
Ω
500 mS/cm
3
112.5
Ω
1000 mS/cm
3
56.3
Ω
2000 mS/cm
3
28.1
Ω
All manuals and user guides at all-guides.com
Содержание 202755
Страница 21: ...21 6 Mounting Sensor component All manuals and user guides at all guides com a l l g u i d e s c o m...
Страница 35: ...35 10 Operation 10 4 Principle of operation Operation in levels All manuals and user guides at all guides com...
Страница 71: ...All manuals and user guides at all guides com a l l g u i d e s c o m...