Recirculating Cooler
11
2.4. Technical
specifications
Eco- Series
SC 5000a
SC 5000w
Working temperature ranges:
Standard unit
°C
+5 ... +35
+5 ... +35
Option Low Temp
°C
-20 ... +35
-20 ... +35
Option Low /HighTemp I
°C
-20 ... +80
-20 ... +80
Option Low /HighTemp II
°C
-20 ... +130
-20 ... +130
Temperature stability
0.1
0.1
A
bsolute
T
emperature
C
alibration
±3 ±3
Heater wattage, Option H5 / H12
kW
5.0 / 12.0
5.0 / 12.0
Cooling capacity
°C
+20 0 -10
+20 0 -10
Medium ethanol
kW
5.0 2.5 1.2
5.0 2.5 1.2
Refrigerant
R404A, R452A*
R404A, R452A*
Pump capacity P3 (Standard) / P4 ** (Option)
see table 1 page 13
Flow rate
P3 / P4
l/min at 0 bar
34 / 42
34 / 42
Pressure max.
P3 / P4
bar at 0 liters
3.2 / 5.2
3.2 / 5.2
Overall dimensions (WxDxH)
cm
59x67/112
59x67/112
Filling volume
liters
43 ... 60
43 ... 60
Weight
kg 153
153
Ambient temperature
°C
5 ... 40
5 ... 40
Mains power connection
V/ Hz
365-440V/3PNPE/50Hz
400/50/3 phases
400/50/3 phases
Current cons. without heater/phase / P3/P4 A
7 (400 V)
7 (400 V)
Current cons.with 5kW heater/phase /P3/P4 A
15(400 V)
15 (400 V)
Current consumption with
12kW heater/phase / P3 / P4
A
30(400 V)
30 (400 V)
Mains power connection
V/ Hz
208-230
V/3PPE/60Hz
208-230/60/3 phases
208-230/60/3 phases
Current cons. without heater/phase / P3
A
9 (208 V) / 8 (230 V)
----
Current cons. without heater/phase / P4
A
12 (208 V) / 13 (230 V)
12 (208 V) / 13 (230 V)
Current cons. 5kW heater/phase / P3
A
23 (208 V) / 22 (230 V)
23 (208 V) / 22 (230 V)
Current cons. 5kW heater/phase / P4
A
25 (208 V) / 26 (230 V)
25 (208 V) / 26 (230 V)
Current cons. 12kW heater/phase / P3
A
37 (208 V) / 39 (230 V)
37 (208 V) / 39 (230 V)
Current cons. 12kW heater/phase / P4
A
41 (208 V) / 43 (230 V)
41 (208 V) / 43 (230 V)
* at 400 V / 50 Hz
All measurements have been carried out at: rated voltage and frequency, ambient temperature: 20 °C
Technical changes without prior notification reserved.
** Pump P4- reduces cooling capacity by 0.3 kW
www.calcert.com
1.800.544.2843
0
5
10
15
20
25
30