JUDO i-soft TGA 2
15
Installation
4.8
Waste water connection and safety overflow hose
The hoses for the regeneration waste water
and the safety overflow must both be routed
kink-free to the water trap (in the scope of
supply). The water trap ensures a free dis-
charge in accordance with DIN EN 1717
(see fig. 10).
The waste water hose with 11 mm outside
diameter must not be routed any higher than
the control head. The hose length must not
exceed 3 m.
The safety overflow hose with 19 mm out-
side diameter must be routed with a steady
drop to the water trap.
If, for on-site reasons, a steady slope to the
water trap can not be realized, then a pump-
ing equipment, which is resistant to saltwa-
ter, must be installed to pump up the regen-
eration waste water.
Fig. 10: Connection to the water trap
Waste water hose
Safety overflow hose
Water trap