Service Manual
1-529
INSTALLATION
9.12 Exception to Setting of Run/Stop Operation
This function is used as an exception to the command: “All Groups Run/Stop” and “Run/Stop by Block”
operations for those selected Groups or Blocks.
Selecting Exception Settings for the Run/Stop Operation (All Groups/Block) are available as follows.
Ɣ
Run and Stop
Ɣ
Run
Ɣ
Stop
Set by Monitor 1 or 2 > Menu > Service Menu > Exception Setting Run/Stop Operation.
Refer to
Section 10.5
for details.
9.13 External Input/Output Setting
The external input/output of each of two terminals are optional.
Their assigned functions are shown below.
Set by Monitor 1 or 2 > Menu > Service Menu > External Input/Output Setting.
Refer to
Section 10.6
for details.
Input and Output
Connection
Function
Input 1
TB3 1-5 Pin
*All Run/Stop (Level)
*Emergency Stop (Level)
*All Run (Pulse)
*Demand Function (Input 1 only)
*All Stop (Pulse)
*No Setting (Factory Setting)
Input 2
TB3 2-5 Pin
Input 3
TB3 3-5 Pin
Input 4
TB3 4-5 Pin
Output 1
TB3 6-8 Pin
*All Run
*All Alarm
*No Setting (Factory Setting)
Output 2
TB3 7-8 Pin
Ŷ([WHUQDO,QSXW)XQFWLRQ
1. All Run/Stop (Level)
All groups simultaneously execute the Run/Stop operation by way of the external input signal.
2. All Run (Pulse)
All groups simultaneously execute the Run operation by way of an external input signal.
3. All Stop (Pulse)
All groups simultaneously Stop operation by the external pulse signal input
Emergency Stop (Level)
All groups simultaneously execute the Stop operation by way of an external emergency stop signal.
While “Emergency Stop” is performed, the wired controller LCD displays “Central Control” and
the operation can not be controlled from the wired controller.
Ɣ
When in use with other large central controllers, the “Run/Stop” operation is available from other
large central controllers even if it is during an emergency stop.
Ɣ
Do not set Emergency Stop when using simultaneously with other central controllers.
None of the “All Run/Stop” and “Run/Stop by Block” commands will be affected when they are set to the
groups/blocks. However, these commands are accepted as follows even if this function is set.
Ɠ
Scheduled Timer Operation
Ɠ
“All Run/Stop” and “Run/Stop by Block” by External Input command
7KH³5XQ6WRS´RSHUDWLRQLVDYDLODEOHZKHQWKHJURXSLVVHOHFWHGLQGLYLGXDOO\
Содержание YVAHP072B31S
Страница 2: ......
Страница 10: ...viii Service Manual ...
Страница 16: ......
Страница 17: ...Service Manual 1 1 INSTALLATION 1 Installation ...
Страница 559: ...Service Manual 1 543 INSTALLATION 7 7RXFK DFN WR QLVK WKLV VHWWLQJ The screen returns to the Service Menu screen 7 ...
Страница 577: ...Service Manual 1 561 INSTALLATION 9 Touch Back to return to the Service Menu screen 9 ...
Страница 920: ......
Страница 921: ...Service Manual 2 1 OPERATION 2 Operation ...
Страница 983: ...Service Manual 2 63 OPERATION Clipped Ceiling Type Grille for Front Discharge 2SWLRQDO Decorative Panel 2SWLRQDO ...
Страница 1184: ...2 264 Service Manual OPERATION 7 Touch on Return to Group sel to return to Setting Group Selection 7 ...
Страница 1315: ...Service Manual 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Страница 1425: ...Service Manual 3 111 TROUBLESHOOTING Surge Absorber SA Surge Absorber SA Surge Absorber SA 3RVLWLRQ RI 6XUJH EVRUEHU 9 9 1 1 1 ...
Страница 1461: ...Service Manual 4 1 MAINTENANCE 4 Maintenance ...
Страница 1657: ...Service Manual 5 1 EXTERNAL INPUT OUTPUT AND FUNCTION SETTING 5 External Input Output and Function Setting ...
Страница 1728: ......
Страница 1729: ...Service Manual 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Страница 1738: ...6 10 Service Manual FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A ft 3 l b ...
Страница 1739: ...SERVICE PARTS LIST Service Manual 7 1 7 Service Parts List ...
Страница 1795: ......
Страница 1796: ... 2015 Johnson Controls Inc SM 15001 ...