Service Manual
1-377
INSTALLATION
12. Operation Mode / Setting Temperature Priority Setting
It is feasible only to set the operation mode and unit temperature setpoint, from one speci
¿
c controller (the main
controller) in the same refrigerant system without having to use the central station. The sub controller will act in
accordance with the settings of the main controller which is effective management of temperature depending on the
interval of the priority operation mode and power saving settings.
1. Press and hold “Menu” and “Back/Help” simultaneously for at least three seconds while in the normal mode (when unit is
not operated). The Test Run menu will be displayed.
2. Select “Priority Setting” from the Test Run menu and press “OK”.
5. Press “Back/Help” on the Test Run menu to return to the normal mode.
3. Press
“ ” to change the settings in the following order “Not available”
ļ
“Operation Mode”
ļ
“Operation Mode” +
Setting Temperature”.
4. Select “YES” and press “OK” to con
¿
rm and display the Test Run menu. If “NO” is pressed, the screen will return to step (3).
Priority Setting
Remote Selection
Controller A (Main)
Controller B and C (Sub)
Operation Mode
Temperature Setpoint
Operation
Mode
Temperature
Setpoint
Without Priority
ż
ż
ż
With Priority
Operation Mode
Ÿ
ż
Operation Mode + Temperature Setpoint
Ÿ
×
ż
: Selection Possible
Ÿ
: Selection Possible Partially
- Operation Mode + FAN set by Controller A (Main)
- Only when COOL mode COOL
ļ
DRY
×
: Selection not possible (Apply to setting temperature of Controller A (Main))
Controller A
(Main)
< Example >
ECO
On/Off
ECO
On/Off
ECO
On/Off
1. This controller comes normally pre-set with factory supplied default settings. It is possible to set, depending on what
is pre-set in the priority settings of the Test Run menu.
2. Only the temperature setting cannot be set as priority. Also, even if operation mode is set as priority, in the case of
COOL/HEAT Automatic mode, the priority will be temporary overridden.
3. When using two controllers, it is not possible to set priority.
4. If one of the devices in the same refrigerant cycle is connected, the main function cannot be used.
Ɣ
Outdoor unit or Indoor unit power saving capabilities are not available.
Ɣ
Receiver Kit
Ɣ
Central Station
Ɣ
Controller set “ON” with the selected operation mode, setting adjustment of Temperature Setpoint, and setting
adjustment for cooling.
Ɣ
Cooling/Heating Changeover Switch Unit
5. It is not possible to operate at the same time cooling and heating mode in the same refrigerant system. If multiple
RC exist within the same refrigerant system, only one RC will give the right to set the operation mode.
Controller B
(Sub)
Controller C
(Sub)
Содержание YVAHP072B31S
Страница 2: ......
Страница 10: ...viii Service Manual ...
Страница 16: ......
Страница 17: ...Service Manual 1 1 INSTALLATION 1 Installation ...
Страница 559: ...Service Manual 1 543 INSTALLATION 7 7RXFK DFN WR QLVK WKLV VHWWLQJ The screen returns to the Service Menu screen 7 ...
Страница 577: ...Service Manual 1 561 INSTALLATION 9 Touch Back to return to the Service Menu screen 9 ...
Страница 920: ......
Страница 921: ...Service Manual 2 1 OPERATION 2 Operation ...
Страница 983: ...Service Manual 2 63 OPERATION Clipped Ceiling Type Grille for Front Discharge 2SWLRQDO Decorative Panel 2SWLRQDO ...
Страница 1184: ...2 264 Service Manual OPERATION 7 Touch on Return to Group sel to return to Setting Group Selection 7 ...
Страница 1315: ...Service Manual 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Страница 1425: ...Service Manual 3 111 TROUBLESHOOTING Surge Absorber SA Surge Absorber SA Surge Absorber SA 3RVLWLRQ RI 6XUJH EVRUEHU 9 9 1 1 1 ...
Страница 1461: ...Service Manual 4 1 MAINTENANCE 4 Maintenance ...
Страница 1657: ...Service Manual 5 1 EXTERNAL INPUT OUTPUT AND FUNCTION SETTING 5 External Input Output and Function Setting ...
Страница 1728: ......
Страница 1729: ...Service Manual 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Страница 1738: ...6 10 Service Manual FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A ft 3 l b ...
Страница 1739: ...SERVICE PARTS LIST Service Manual 7 1 7 Service Parts List ...
Страница 1795: ......
Страница 1796: ... 2015 Johnson Controls Inc SM 15001 ...