JOHNSON CONTROLS
92
FORM100.50-EG12 (918)
Warranty:
Manufacturer shall warrant all equipment and material of its manufacture
against defects in workmanship and material for a period of eighteen (18) months from
date of shipment.
1. The warranty shall include parts only during this period.
2. The warranty shall not include parts associated with routine maintenance, such as
belts, air filters, etc.
Delivery and Handling
Unit shall be delivered to the job site fully assembled, wired, and charged with refrigerant
and oil by the manufacturer.
Unit shall be stored and handled per Manufacturer’s instructions.
All handling and storage procedures shall be per manufacturer’s recommendations.
Submittals
Shop Drawings:
Shop drawing submittals shall include, but not limited to, the following:
drawings indicating components, dimensions, weights, required clearances, and location,
type and size of field connections, and power and control wiring connections.
Product Data:
Product data shall include dimensions, weights, capacities, ratings, fan
performance, motor electrical characteristics, and gauges and finishes of materials.
Documentation:
1.
Fan curves with specified operating point clearly plotted shall be provided.
2.
Product data of filter media, filter performance data, filter assembly, and filter frames
shall be provided.
3.
Electrical requirements for power supply wiring; including wiring diagrams for inter
-
lock and control wiring shall be supplied. Factory and field-installed wiring shall be
clearly indicated.
4. Operation and maintenance documentation shall be supplied in accordance with
Section 01830 – Operation and Maintenance, including but not limited to instruc-
tions for lubrication, filter replacement, compressor, motor and drive replacement,
coil cleaning, filter maintenance, spare parts lists, and wiring diagrams.
Warranties
Equipment shall include the manufacturer’s warranty not less than eighteen months from
the date of shipment.
Extended parts warranty [optional] shall be included for an additional 1 [5] years
Extended parts and labor warranty [optional] shall be included for an additional 1 [5] years
EQUIPMENT
Product Specification
Summary:
Completely factory assembled unitized construction packaged single package
unit air conditioning unit including a factory-mounted and wired unit controller and sen-
sors, single-point power connection 460V [208V/230V/575V] three-phase, 60Hz power
supply, outdoor air handling section with return and supply openings, discharge plenum,
direct-expansion refrigerant condensing section.
Guide Specifications (Cont'd)