JOHNSON CONTROLS
56
FORM100.50-EG12 (918)
Exhaust Fan Data
EXHAUST FAN MOTOR SIZING INSTRUCTIONS
In order to determine the proper exhaust fan motor size, add the return duct static pres-
sure to the appropriate damper pressure drop value in
Table 16 on page 53
to get the
total static pressure applied to the exhaust fan. Based on the exhaust fan airflow and total
static pressure, determine the brake horsepower (BHP) and RPM of the exhaust fan.
TABLE 22 -
DUAL 18 X 18 FORWARD-CURVED FAN
TOTAL STATIC PRESSURE (IWG)
CFM
STD. AIR
0.25
0.50
0.75
1.00
1.25
1.50
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
6000
0.4
291
0.7
398
1.1
501
1.6
596
2.1
683
2.7
763
8000
0.7
316
1.1
406
1.5
485
1.9
566
2.4
643
3.0
717
10000
1.2
349
1.6
429
2.1
499
2.5
562
3.0
627
3.6
691
12000
1.9
392
2.3
456
2.9
522
3.4
581
3.9
635
4.5
688
14000
2.8
435
3.3
491
3.9
549
4.5
605
5.1
656
5.7
704
16000
3.9
476
4.6
533
5.1
579
5.9
631
6.6
681
7.3
727
18000
5.2
517
6.2
577
6.7
619
7.4
661
8.3
707
9.1
752
20000
7.0
560
8.0
619
8.8
662
9.4
698
10.2
737
11.2
779
22000
9.1
604
10.1
660
11.3
706
12.0
740
12.7
773
13.6
809
24000
11.7
648
12.7
701
14.0
748
26000
14.7
693
NOTE:
For performance at operating points not included in these tables, consult your local Johnson Controls representative.
TABLE 23 -
EXHAUST FAN PERFORMANCE
FAN TYPE
18X18
20X18
YPAL070–080
X
X
YPAL090–105
X
X
TABLE 24 -
DUAL 20 X 18 FORWARD-CURVED FAN
TOTAL STATIC PRESSURE (IWG)
CFM
STD. AIR
0.25
0.50
0.75
1.00
1.25
1.50
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
12000
1.3
295
1.9
373
2.5
445
3.2
514
3.9
577
4.6
635
14000
1.9
318
2.5
388
3.2
453
3.9
515
4.7
574
5.5
630
16000
2.6
344
3.3
407
4.1
466
4.9
522
5.7
576
6.6
629
18000
3.5
371
4.3
429
5.1
483
6.0
535
6.9
584
7.8
633
20000
4.6
399
5.4
453
6.4
503
7.3
551
8.3
597
9.3
642
22000
5.9
428
6.8
478
7.8
525
8.8
570
9.9
613
11.0
654
24000
7.5
458
8.5
505
9.5
549
10.6
591
11.7
631
12.9
670
26000
9.4
488
10.4
532
11.5
574
12.7
613
13.9
652
15.1
689
28000
11.5
519
12.6
560
13.8
600
15.0
637
16.3
673
17.6
709
30000
13.9
551
15.2
589
16.4
626
17.7
662
19.0
697
20.4
730
32000
16.7
583
18.1
618
19.4
654
20.7
688
22.1
721
23.6
753
34000
19.9
615
21.3
648
22.7
682
24.1
715
25.6
746
36000
23.4
647
24.9
679
26.4
710
27.9
742
NOTE:
For performance at operating points not included in these tables, consult your local Johnson Controls representative.